1-866-311-1945 sales@excessups.com

United States United States [change]
29% Off

Eaton Powerware 9130 Rackmount UPS 3000VA PW9130L3000R-XL2U

Eaton Powerware 9130 Rackmount UPS 3000VA   
Model: PW9130L3000R-XL2U
Online Double Conversion 3000VA / 2700W, 120V
Refurbished with New Batteries
1 Year Extended Warranty Included

Availability: In stock

Msrp Price: $1,392.99

Now only: $994.99

Shipping Info
  • This item is in stock and ships within 1 business day
  • We will gladly accept returns for any reason within 30 days of receipt of delivery
  • Continental USA & Canada

Description

Details

Manufacturer:  Eaton Powerware 9130 Rackmount UPS 3000VA    
Model: PW9130L3000R-XL2U Refurbished
Condition: Refurbished with New Batteries
Part Number: PW9130L3000R-XL2U
Warranty: 1 Year Extended Warranty, additional warranty available

The PW9130L3000R-XL2U is refurbished and comes with fresh new batteries. The PW9130L3000R-XL2Ucomes with a one year replacement warranty. Additional warranty of up to 3 years is available for your convenience.


PW9130L3000R-XL2U Specifications:

 

General

Topology

Online, double-conversion

Configuration

Rackmount

Catalog Number

PW9130L3000R-XL2U

Color

Black

Rating (VA/Watts)

3000/2700

Diagnostics

Full system self-test

Efficiency

>95% in high-efficiency mode; >86% in online mode

UPS Bypass

Automatic bypass

Dimensions (H x W x D, inches)

3.4 x 17.2 x 23.6

Weight (lbs)

65

Rail Kit Included

Included with all rackmount units

Remote Emergency Power off (REPO)

Emergency shutdown control through the REPO port

Contents
(Ships with the following items)

1 ready-to-go UPS
Software Suite CD
USB Cable
User Guide
Quick Start Instructions
4-post Rail Kit

Electrical Input

Connection

(1) NEMA L5-30P

Input Cord

6 ft 

Input Voltage Range

90-138 Vac

Nominal Voltage

120V

Frequency

50/60 Hz

Frequency Range

45–65 Hz

Nominal Current

25A

Breaker Ratings

30A

Generator Compatability

Yes

Electrical Output

Output Receptacles

(4) NEMA 5-20R
(1) NEMA L5-30R

On Utility Voltage Regulation

±3% of nominal

On Battery Voltage Regulation

±3% of nominal

Voltage Wave

Shape (On Battery)

Sine wave

Power Factor

0.9

Frequency Regulation

±3% Hz online

Load Crest Factor

3 to 1

Battery

Optional Extended

Battery Module

PW9130N3000R-EBM2U

Maximum number of 

extended battery modules

(EBM)

4

Battery Type

72 Vdc; (6) 12V, 9 Ah

Battery Replacement

Hot-swappable internal and external batteries

Start On Battery

Allows start of UPS without utility input

Recharge Time

Internal batteries: 3 hours. 1 EBM: 9 hours; 2 EBM: 15 hours; 3 EBM: 21 hours; 4 EBM: 27 hours

 

Communications

User Interface

Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish

LEDs

Four status-indicating LEDs

Communication Ports

(1) USB, (1) RS-232 serial, Relay output (common alarm standard)

Communications Slot

Optional communication slots (BD Slot)

Optional Communication

Cards

SNMP/Web card for direct control and monitoring in SNMP-based networks, monitoring of UPS status and meters through Web browser interface Relay card for integration to industrial environment and building management systems, remote shutdown for IBM AS/400 systems

Power Management

Software

Bundled software suite CD

 

Environmental & Standards

RoHS Compliance

Yes

Heat Dissipation (BTU)

Line: 1257, Bat: 1755

Audible Noise

<50 dB

Operating Temperature

0°C to 40°C(32°F to 104°F) in online mode, with linear derating for altitude. NOTE:Thermal protection switches load to bypass in case of overheating

Safety markings

UL, cUL, VCCI

EMC Markings

FCC Class A, EN55022 Class A

Storage Temperature

-20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131 °F) without batteries

Relative Humidity

5–90% non-condensing

Additional Info

Additional Info

Input No
Output(VA) No
Type No
Output Voltage No