Tripp Lite SmartOnline 2.2kVA SU2200XLA

SU2200XLA Refurbished SmartOnline UPS
2.2kVA Online Double Conversion UPS, Tower, 110/120v NEMA outlets
Refurbished with New Batteries


 



  • 2200VA / 2.2kVA / 1600 watt on-line double-conversion tower UPS

  • 110/120V +/-2% output at 50/60Hz, high efficiency economy mode option

  • Expandable runtime, Hot-swappable battery modules

  • USB, RS232 & EPO ports; support for SNMP/WEB card options

  • Front panel status LEDs with detailed load and battery metering

  • 2 independently switchable output load banks

  • NEMA 5-20P input; L5-20R & 5-15/20R outlets

Availability: In stock

$684.99
Shipping Info
  • This item is in stock and ships within 1 business day
  • We will gladly accept returns for any reason within 30 days of receipt of delivery
  • Continental USA & Canada

Description

Details

Manufacturer: Tripp Lite
Model:  SU2200XLA Refurbished SmartOnline UPS 2.2kVA Online Double Conversion UPS, Tower, 110/120v NEMA outlets
Condition: Refurbished with New Batteries
Part Number: SU2200XLA
Warranty: 1 Year Full Replacement Warranty, additional warranty available

 

SU2200XLA Specifications:

 

OUTPUT

Output Volt Amp Capacity (VA)

2200

Output kVA capacity (kVA)

2.2

Output Watt Capacity (watts)

1600

Output kW capacity

1.6

Output power factor

0.7

Crest Factor

3:1

Nominal Output Voltage(s) Supported

110V; 120V

Nominal Voltage details

120V default

Frequency compatibility

50 / 60 Hz

Frequency compatibility details

Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start

Output voltage regulation (line mode)

+/- 2%

Output voltage regulation (Economy line mode)

+/- 10%

Output voltage regulation (Battery mode)

+/- 2%

Built-in UPS output receptacles

6 5-15/20R outlet(s); 1 L5-20R outlet(s)

Built-in controllable switched load banks

Two switchable three-outlet 5-15/20R load banks

Output AC waveform (AC mode)

Sine wave

Output AC waveform (battery mode)

Pure Sine wave

INPUT

Rated input current (at maximum load)

16A (120V), 17.6A (110V)

Nominal Input Voltage(s) Supported

110V AC; 120V AC

UPS input connection type

5-20P

Input circuit breaker

30A

UPS Input cord length (ft.)

10

UPS Input cord length (m)

3

Recommended Electrical Service

20A 120V

Phase

Single-Phase

BATTERY

Full load runtime (minutes)

4.5 min. (1600w)

Half load runtime (minutes)

14 min. (800w)

Expandable battery runtime

Extended runtime supported via optional external battery packs

External battery pack compatibility

BP48V24-2U (limit 1); BP48V60RT-3U (multi-pack compatible); BP48V27-2US (multi-pack compatible)

DC system voltage (VDC)

48

Battery recharge rate (included batteries)

Less than 5 hours from 10% to 90%

Replacement battery cartridge (internal UPS battery replacement)

RBC48-SUTWR

Battery Access

Battery access door

Battery replacement description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation description

Online, double-conversion power conditioning

Overvoltage correction

2% output voltage regulation during overvoltages to 150

Undervoltage correction

2% output voltage regulation during undervoltages to 80

Severe undervoltage correction

2% output voltage regulation during undervoltages to 65 (under 70% load only)

LEDS ALARMS & SWITCHES

LED Indicators

14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information - includes 4-LED meter display for load and battery charge level

Alarms

Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions

Alarm cancel operation

Power-fail alarm can be silenced using alarm-cancel switch

Switches

2 switches control off/on power status and alarm-cancel/self-test operation

SURGE / NOISE SUPPRESSION

UPS AC suppression joule rating

570

UPS AC suppression response time

Instantaneous

UPS Dataline suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet

EMI / RFI AC noise suppression

Yes

PHYSICAL

Installation form factors supported with included accessories

Tower

Primary form factor

Tower

UPS / Power Module dimensions in primary form factor (height x width x depth / inches)

10.2 x 9 x 19.5

UPS / Power Module dimensions in primary form factor (height x width x depth / cm)

26 x 22.9 x 49.5

UPS / Power Module weight (lbs)

52.7

UPS / Power Module weight (kg)

23.9

UPS Shipping dimensions (height x width x depth / inches)

15.2 x 13 x 24

UPS Shipping dimensions (height x width x depth / cm)

38.7 x 33 x 61

Shipping weight (lbs)

59.5

Shipping weight (kg)

27

Cooling method

Fan

UPS housing material

Steel

ENVIRONMENTAL

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full load)

812.9

AC economy mode BTU / hr. (full load)

347.2

Battery mode BTU / hr. (full load)

885.6

AC economy mode efficiency rating (100% load)

94%

Audible Noise

< 45 dB at front side 1m

COMMUNICATIONS

Communications interface

USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring port description

Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications

PowerAlert software

Included

Communications cable

USB and DB9 cabling included

WatchDog compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Low voltage transfer to battery power (setpoint)

80V (100% load), 65V ( <70% load)

High voltage transfer to battery power (setpoint)

150

SPECIAL FEATURES

Cold Start (startup in battery mode during a power failure)

Cold-start operation supported

High availability UPS features

Automatic inverter bypass; Hot swappable batteries

Green & high efficiency features

High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation

CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)