Call toll free: 1-866-311-1945 | sales@excessups.com
Your Region:

Eaton Powerware 5130 Rack/Tower UPS 2500VA PW5130L2500-XL2U

Eaton Powerware 5130 Rack/Tower UPS 2500VA 
Model: PW5130L2500-XL2U
Refurbished with New Batteries
1 Year Extended Warranty Included
$649.99
Availability: In stock

Description

Details

Manufacturer: Powerware 5130 Rack/Tower UPS 2500VA 
Model: PW5130L2500-XL2U
Condition: Refurbished with New Batteries
Part Number: PW5130L2500-XL2U
Warranty: 1 Year Extended Warranty, additional warranty available

The PW5130L2500-XL2U comes refurbished with new batteries. The Eaton UPS comes with a one year replacement warranty. Additional warranty of up to 3 years is available for your convenience.


PW5130L2500-XL2U Specifications:

 

General

LEDs

13 status-indicating LEDs

Topology

Line interactive

Diagnostics

Full system self-test at power up

Transfer Time

1–4 ms typical

ROO/RPO

Rear deck emergency stop connector (for remote on/off and power off)

Rail Kit/Tower Stand

Included with all units

Electrical Input

Nominal Voltage

120V

Voltage Range

120V: 89–151 Vac

Frequency

50/60 Hz

Frequency Range

47–70 Hz for 50 Hz operation
56.5–70 Hz for 60 Hz operation

Power Draw of UPS (full load)

2500: 20.8A @120V, 10.9A @230V

Electrical Output

Power Factor

0.9

On Utility Voltage Regulation

120V: 102–132 Vac
230V: 184–265 Vac

On Battery Voltage Regulation

-10%, +6% of nominal

Efficiency

Normal or line mode: >94%
On battery: 70% (1250–1750 VA), 75% (2500–3000 VA)

Frequency Regulation

0.1 Hz

Over Current Protection

Electronic current limit

Load Crest Factor

3:1

Load Segments

Two individually controlled output receptacles

Battery

Internal Battery Type

1250/2500 VA: 12V/7.2 Ah; sealed, lead-acid; maintenance free
1750/3000 VA: 12V/9 Ah; sealed, lead-acid; maintenance free

EBM Battery Type

12V/9 Ah

Battery Runtime

1250 VA: 5 min w/internal batteries @100% load (0.9 PF)
1750 VA: 3.5 min w/internal batteries @100% load (0.9 PF)
2500–3000 VA: 3 min w/internal batteries @100% load (0.9 PF)

Battery Replacement

Hot-swappable internal batteries

Start-On-Battery

Allows start of UPS without utility input

Communications

Serial Port

RS-232 (RJ45) ports

USB Port

As standard (HID)

Optional Communications Slots

ConnectUPS-MS network management card and ModBus

Cables

RS-232 and USB 6-foot communications cables included

Power Management Software

Eaton Software Suite CD-ROM (bundled with UPS)

Environmental 

Safety Markings

120V: UL; cUL
230V: C-Tick; CE, TUV, cUL, UL

Safety Conformance

120V: UL 1778; UL497A; cUL (CAN/CSA C22.2, No. 107.1)
230V: UL1778, UL 497A (data line only); cUL (CAN/CSA C22.2, No. 107.1); EN 50091-1-1 and IEC 60950

EMC Compliance

120V: FCC Part 15 subpart B Class A
230V: EN 50091-2. FCC Part 15 subpart J Class A

Operating Temperature

1250 VA: 0˚C (32˚F) to +40˚C (104˚F)
1750–3000 VA: 0˚C (32˚F) to +35°C (95˚F)

Storage Temperature

-15˚C (5˚F) to +50˚C (122˚F)

Relative Humidity

20–95% non-condensing

Surge Suppression

ANSI C62.41 Category A (formerly IEEE 587)

Audible Noise

Max 45 dBA

Altitude

Up to 10,000 ft (3000M) without de-rating

 

Additional Info

Additional Info

Manufacturer No
Form Factor No
Waveform in Battery Mode No
Input Voltage No
Output (VA) No
Output Voltage No
PDU Total Outlets No