1-866-311-1945 sales@excessups.com

United States United States [change]

Tripp Lite Smart-Online UPS 3000VA 120V SU3000RTXR3U - Refurbished

Refurbished Tripp Lite Smart-Online UPS 3000VA SU3000RTXR3U
Model: SU3000RTXR3U
Input: NEMA L5-30P (120V 30A)
Output:
(4) NEMA 5-15R (4) NEMA 5-15/20R (1) L5-30R
Double-Conversion UPS - Pure Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included

Availability: Sold Out

$499.99
Shipping Info
  • This item is in stock and ships within 1 business day
  • We will gladly accept returns for any reason within 30 days of receipt of delivery
  • Continental USA & Canada

Description

Details

Manufacturer: Tripp Lite
Model:
Refurbished Tripp Lite Smart-Online
UPS 3000VA 120V with New Batteries
Condition:
New batteries, refurbished UPS
Part Number:
SU3000RTXR3U

Maximum output: 3000VA / 2400W
Typical backup time
at half load: 30 minutes (1200 Watts)
Typical backup time
at full load: 12 minutes (2400 Watts)
Warranty:
1 year full replacement warranty


Tripp Lite Smart-Online UPS 3000VA SU3000RTXR3U Manual


SU3000RTXR3U - Tripp Lite Smart-Online UPS 3000VA Specifications:

 

OUTPUT

Output Volt Amp Capacity (VA)

3000

Output kVA Capacity (kVA)

3

Output Watt Capacity (Watts)

2400

Output kW Capacity (kW)

2.4

Output Capacity Details

OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% load for 3 minutes; 150% load for 30 seconds and >150% load for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits)

Power Factor

0.8

Crest Factor

3:1

Nominal Output Voltage(s) Supported

110V; 120V

Nominal Voltage Details

120V default

Frequency Compatibility

50 / 60 Hz

Frequency Compatibility Details

Output frequency matches input nominal on startup, defaults to 60 Hz on cold-start

Output Voltage Regulation (Line Mode)

+/- 2%

Output Voltage Regulation (Economy Line Mode)

+/- 10%

Output Voltage Regulation (Battery Mode)

+/- 2%

Output Receptacles

(4) 5-15R; (4) 5-15/20R; (1) L5-30R

Load Management Receptacles

Two switchable four-outlet load banks, (bank 1 - four 5-15/20R, bank 2 - four 5-15R outlets)

Output Circuit Breakers

15A branch rated (x2) - each breaker protects 4 outlets, L5-30R is unbreakered

Output AC Waveform (AC Mode)

Sine wave

Output AC Waveform (Battery Mode)

Pure Sine wave


INPUT

Rated input current (Maximum Load)

24A

Nominal Input Voltage(s) Supported

110V AC; 120V AC

UPS Input Connection Type

L5-30P

Input Circuit Breakers

40A

UPS Input Cord Length (ft.)

10

UPS Input Cord Length (m)

3.0

Recommended Electrical Service

30A 120V

Input Phase

Single-Phase


BATTERY

Full Load Runtime (min.)

12 min. (2400w)

Half Load Runtime (min.)

30 min. (1200w)

Expandable Battery Runtime

Supports extended runtime with optional external battery packs

External Battery Pack Compatibility

BP72V15-2U(limit 1); BP72V28RT-3U(multi-pack compatible); BP72V18-2US(multi-pack compatible)

DC System Voltage (VDC)

72

Battery Recharge Rate (Included Batteries)

Less than 6 hours from 10% to 80% (typical, full load discharge)

Internal UPS Replacement Battery Cartridge

RBC96-3U(quantity 2)

Battery Access

Front panel battery access door

Battery Replacement Description

Hot-swappable, user replaceable batteries

Expandable Runtime

Yes


VOLTAGE REGULATION

Voltage Regulation Description

Online, double-conversion power conditioning

Overvoltage Correction

2% output voltage regulation during overvoltages to 150

Undervoltage Correction

2% output voltage regulation during undervoltages to 80

Severe Undervoltage Correction

2% output voltage regulation during undervoltages to 65 (under 70% load only)


USER INTERFACE, ALERTS & CONTROLS

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation

Alarm Cancel Operation

Power-fail alarm can be silenced using alarm-cancel switch

Audible Alarm

Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions

LED Indicators

14 LEDs indicate line power, online mode, economy/bypass mode, on-battery, overload, battery low, replace battery and fault status information; 4-LED meter displays load and battery charge levels; LED panel rotates for viewing in rack/tower formats


SURGE / NOISE SUPPRESSION

UPS AC Suppression Joule Rating

480

UPS AC Suppression Response Time

Instantaneous

UPS Dataline Suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet

EMI / RFI AC Noise Suppression

Yes


PHYSICAL

Primary Form Factor

Rackmount

UPS Power Module Dimensions (hwd, cm)

13.21 x 45.21 x 66.04

Rack Height (U Spaces)

3

Minimum Required Rack Depth (cm)

93.98

UPS Power Module Weight (kg)

50.48

UPS Shipping Dimensions (hwd / cm)

28.45 x 58.42 x 80.01

Shipping Weight (kg)

68.1

Cooling Method

Fan

UPS Housing Material

Steel

Minimum Required Rack Depth (mm)

940

Primary UPS Height (mm)

132

Primary UPS Width (mm)

452

Primary UPS Depth (mm)

660

Shipping Height (mm)

284

Shipping Width (mm)

584

Shipping Depth (mm)

800


ENVIRONMENTAL

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.

Relative Humidity

0 to 95%, non-condensing

AC Mode BTU / Hr. (Full Load)

1117

AC Economy Mode BTU / Hr. (Full Load)

253

Battery Mode BTU / Hr. (Full Load)

1224

AC Mode Efficiency Rating (100% Load)

88%

AC Economy Mode Efficiency Rating (100% Load)

97%


COMMUNICATIONS

Communications Interface

USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface

Network Management Cards

SNMPWEBCARD; TLNETCARD; WEBCARDLX;MODBUSCARD; RELAYIOCARD

(NOT INCLUDED)

Network Monitoring Port Description

Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications; Economy-mode setting option is available using PowerAlert software and DB9 Serial cable connection OR via select Network Management Card options (NOT INCLUDED)

PowerAlert Software

For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert

Communications Cable

USB and DB9 cabling included (NOT INCLUDED)

WatchDog Compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications


LINE / BATTERY TRANSFER

Transfer Time

No transfer time (0 ms.) in online, double-conversion mode

Low Voltage Transfer to Battery Power (Setpoint)

80V (100% load), 65V ( <70% load)

High Voltage Transfer to Battery Power (Setpoint)

150


SPECIAL FEATURES

Cold Start (Startup in Battery Mode During a Power Failure)

Cold-start operation supported

High Availability UPS Features

Automatic inverter bypass; Hot swappable batteries

Green Energy-Saving Features

High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation


CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)

 


Additional Info

Additional Info

Manufacturer Tripp Lite
Form Factor Rackmount
Waveform in Battery Mode Pure Sinewave
Input Voltage 120V AC
Output (VA) 3000VA
Output Voltage 120V AC