Description
Details
Manufacturer: Tripp Lite
Model: Tripp Lite SmartPro UPS 2200VA 1920W, RM, 20A, 120V
Condition: New batteries, refurbished UPS
Part Number: SMART2200RM2U
Maximum output: 1920W / 2200VA
Typical backup time at half load: 12 minutes (960 Watts)
Typical backup time at full load: 4.5 minutes (1920 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartPro 2200VA 1920W RM 120V SMART2200RM2U Manual
SMART2200RM2U - Tripp Lite SmartPro 2200VA Specifications:
Input:
Rated input current (Maximum Load) |
16A (120V) |
||
Nominal Input Voltage(s) Supported |
120V AC |
||
UPS Input Connection Type |
|
||
Input Circuit Breakers |
20A |
||
UPS Input Cord Length (ft.) |
10 |
||
UPS Input Cord Length (m) |
3.1 |
||
Recommended Electrical Service |
20A 120V |
||
Input Phase |
Single-Phase |
Output:
Output Volt Amp Capacity (VA) |
2200 |
||||
Output kVA Capacity (kVA) |
2.2 |
||||
Output Watt Capacity (Watts) |
1920 |
||||
Output kW Capacity (kW) |
1.92 |
||||
Power Factor |
87 |
||||
Nominal Voltage Details |
120v nominal output in battery mode |
||||
Frequency Compatibility |
60 Hz |
||||
Output Voltage Regulation (Line Mode) |
-14%, +6% |
||||
Output Voltage Regulation (Battery Mode) |
+/- 5% |
||||
Load Management Receptacles |
Two switchable single-outlet load banks |
||||
Output AC Waveform (AC Mode) |
Pure Sine wave |
||||
Output AC Waveform (Battery Mode) |
Pure Sine wave |
||||
Nominal Output Voltage(s) Supported |
110V; 115V; 120V |
||||
Output Receptacles |
|
||||
Individually Controllable Load Banks |
Yes |
Battery:
Full Load Runtime (min.) |
4.5 min. (1920W) |
Half Load Runtime (min.) |
12 min. (960w) |
DC System Voltage (VDC) |
48 |
Battery Recharge Rate (Included Batteries) |
Less than 4.5 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC94-2U |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
No |
Voltage Regulation:
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83 to 145 |
Overvoltage Correction |
Input voltages between 127 and 145 are reduced by 12% |
Undervoltage Correction |
Input voltages between 108 and 96 are boosted by 12% |
Severe Undervoltage Correction |
Input voltages between 83 and 95 are boosted by 24% |
User Interface, Alerts & Controls:
Front Panel LCD Display |
Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, |
Switches |
3 pushbutton switches control OFF / ON power status, MODE selection and MUTE / ENTER control functions |
Alarm Cancel Operation |
Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available |
Audible Alarm |
Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown |
Surge / Noise Suppression:
UPS AC Suppression Joule Rating |
570 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
Physical:
Cooling Method |
Fan
|
Included Mounting Accessory Description |
Not included
|
Installation Form Factors Supported |
4 post 19 inch rackmount
|
Installation Form Factors Supported |
2 post rackmount ( 2POSTRMKITWM ); 2-4 post front rail rackmount ( UPSHDEARKIT ); 4 post rackmount short-depth ( 4POSTRAILKITWM ); Tower ( 2- 9USTAND ); Wallmount ( 2POSTRMKITWM )
|
Minimum Required Rack Depth (cm) |
62.13
|
Minimum Required Rack Depth |
24.46
|
Optional Mounting Accessory Notes |
Optional 2-9USTAND enables upright tower UPS placement; 2POSTRMKITWM enables wall-mount and 2-post rackmount installation; 4POSTRAILKITWM enables installation in 4-post short-depth racks from 14.5 to 23.5 inches (368 to 597mm); UPSHDEARKIT enables installation in 2 or 4-post racks using front vertical rails only, without rear support
|
Primary Form Factor |
Rackmount
|
Primary UPS Depth (mm) |
494
|
Primary UPS Height (mm) |
87 |
Primary UPS Width (mm) |
440 |
Rack Height |
2U |
Shipping Dimensions (hwd / cm) |
22.61 x 61.72 x 54.10 |
Shipping Dimensions (hwd / in.) |
8.90 x 24.30 x 21.30 |
Shipping Weight (kg) |
35.29 |
Shipping Weight (lbs.) |
77.80 |
UPS Housing Material |
Steel |
UPS Power Module Dimensions (hwd, cm) |
8.71 x 43.99 x 49.43 |
UPS Power Module Dimensions (hwd, in.) |
3.43 x 17.32 x 19.46 |
UPS Power Module Weight (kg) |
26.13 |
UPS Power Module Weight (lbs.) |
57.6 |
Environmental:
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
0 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
306 |
Battery Mode BTU / Hr. (Full Load) |
1157 |
AC Mode Efficiency Rating (100% Load) |
96% |
Audible Noise |
60 dBA at front side 1 meter |
Communications:
Network Management Cards |
Not included: (Optional) |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert |
Communications Cable |
USB, DB9 and EPO cabling included |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
Network UPS Tools Compatibility |
NUT compatible. See the full list of Tripp Lite NUT compatible UPS systems at http://www.networkupstools.org/stable-hcl.html?manufacturer=Tripp Lite |
Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |
Additional Info
Additional Info
Manufacturer | Tripp Lite |
---|---|
Form Factor | Rackmount |
Waveform in Battery Mode | Pure Sinewave |
Input Voltage | 120V AC |
Output (VA) | 2200VA |
Output Voltage | 120V AC |
PDU Total Outlets | No |