Description
Details
Manufacturer: Tripp Lite
Model: Tripp Lite SmartPro UPS 5000VA 3750W, RM, 30A, 208V Input, 208/120V Output
Condition: New batteries, refurbished UPS
Part Number: SMART5000XFMRXL
Maximum output: 3750W / 5000VA
Typical backup time at half load: 20 minutes (1875 Watts)
Typical backup time at full load: 8.5 minutes (3750 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartPro 5000VA 3750W RM 3U 208/120V SMART5000XFMRXL Manual
SMART5000XFMRXL - Tripp Lite SmartPro 5000VA Specifications:
Input:
Rated input current (Maximum Load) |
24A |
||
Nominal Input Voltage(s) Supported |
208V AC |
||
UPS Input Connection Type |
|
||
Input Circuit Breakers |
20A |
||
UPS Input Cord Length (ft.) |
10 |
||
UPS Input Cord Length (m) |
3.1 |
||
Recommended Electrical Service |
30A 208V |
||
Input Phase |
Single-Phase |
Output:
Output Volt Amp Capacity (VA) |
5000 |
||||||
Output kVA Capacity (kVA) |
5 |
||||||
Output Watt Capacity (Watts) |
3750 |
||||||
Output kW Capacity (kW) |
3.75 |
||||||
Power Factor |
0.75 |
||||||
Nominal Voltage Details |
208/120V nominal output in battery mode |
||||||
Frequency Compatibility |
60 Hz |
||||||
Output Voltage Regulation (Line Mode) |
208 & 120V (+/- 10%) |
||||||
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
||||||
Output Voltage Regulation (Battery Mode) |
+/- 5% |
||||||
Load Management Receptacles |
Eight switchable single-outlet 5-15/20R load banks |
||||||
Output Circuit Breakers |
20A double pole breaker supports L6-20R outlets, 20A branch rated breaker (x2) supports 4 5-15/20R outlets each, L6-30R outlet is unbreakered |
||||||
Output AC Waveform (AC Mode) |
Sine wave |
||||||
Output AC Waveform (Battery Mode) |
Pure Sine wave |
||||||
Nominal Output Voltage(s) Supported |
110V; 115V; 120V; 208V |
||||||
Output Receptacles |
|
||||||
Individually Controllable Load Banks |
Yes |
Battery:
Full Load Runtime (min.) |
8.5 min. (3750w) |
Half Load Runtime (min.) |
20 min. (1875w) |
Expandable Battery Runtime |
Extended runtime supported via optional external battery packs |
External Battery Pack Compatibility |
BP48V27-2US (multi-pack compatible); BP48V60RT-3U (multi-pack compatible) |
DC System Voltage (VDC) |
48 |
Battery Recharge Rate (Included Batteries) |
6.8 hours from 10% to 90% (typical, full load discharge) |
Internal UPS Replacement Battery Cartridge |
RBC94-3U (quantity 3) |
Battery Access |
Front panel battery access door |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Expandable Runtime |
Yes |
Voltage Regulation:
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 167 to 260 |
Overvoltage Correction |
Input voltages between 228 and 260 are reduced by 12% |
Undervoltage Correction |
Input voltages between 167 and 194 are boosted by 12% |
User Interface, Alerts & Controls:
Switches |
2 Switches control off/on power status and alarm-cancel/self-test operation |
Alarm Cancel Operation |
Power-fail alarm can be silenced using alarm-cancel switch; once silenced, alarm will re-sound to indicate lowbattery status |
Audible Alarm |
Audible alarm indicates power-failure, overload and low-battery conditions |
LED Indicators |
5 LEDs indicate line power, battery power, overload, voltage regulation and battery low/replace status |
Surge / Noise Suppression:
UPS AC Suppression Joule Rating |
1020 |
UPS AC Suppression Response Time |
Instantaneous |
EMI / RFI AC Noise Suppression |
Yes |
Physical:
Cooling Method |
Fan
|
Installation Form Factors Supported with Included Accessories |
4 post 19 inch rackmount
|
Installation Form Factors Supported with Optional Accessories |
2 post rackmount ( 2POSTRMKITHD ); Tower ( 2-9USTAND )
|
Minimum Required Rack Depth with External Battery Pack (cm) |
81
|
Minimum Required Rack Depth with External Battery Pack (in.) |
32
|
Minimum Required Rack Depth without External Battery Pack (cm) |
76
|
Minimum Required Rack Depth without External Battery Pack (in.) |
30
|
Primary Form Factor |
Rackmount
|
Primary UPS Depth (mm) |
635
|
Primary UPS Height (mm) |
132 |
Primary UPS Width (mm) |
445 |
Rack Height |
3U |
Shipping Dimensions (hwd / cm) |
30.48 x 58.42 x 83.82 |
Shipping Dimensions (hwd / in.) |
12.00 x 23.00 x 33.00 |
Shipping Weight (kg) |
83.91 |
Shipping Weight (lbs.) |
185.00 |
UPS Housing Material |
Steel |
UPS Power Module Dimensions (hwd, cm) |
13.21 x 44.45 x 63.50 |
UPS Power Module Dimensions (hwd, in.) |
5.2 x 17.5 x 25 |
UPS Power Module Weight (kg) |
65.00 |
UPS Power Module Weight (lbs.) |
143.3 |
Environmental:
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
5 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
366 |
AC Mode Efficiency Rating (100% Load) |
97% |
Audible Noise |
45 dBA maximum, front side 1m |
Communications:
Network Management Cards |
|
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at http://www.tripplite.com/poweralert |
Communications Cable |
USB |
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
Communications Interface |
DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB |
Additional Info
Additional Info
Manufacturer | Tripp Lite |
---|---|
Form Factor | Rackmount |
Waveform in Battery Mode | Pure Sinewave |
Input Voltage | 208V AC |
Output (VA) | 5000VA |
Output Voltage | 120V AC, 208V AC |
PDU Total Outlets | No |