Tripp Lite SmartOnline 16kVA SU16000RT4U

SU16000RT4U Refurbished SmartOnline UPS
16kVA Online Double Conversion UPS, 8U Rack/Tower, 208/120V or 240/120V Hardwire+NEMA Outputs, Split phase input
Refurbished with New Batteries


 



  • 16kVA / 16,000VA / 11,200W on-line double-conversion UPS, split phase input

  • 208/120V or 240/120V +/-3% output at 60Hz

  • 8U Rack/Tower compatible; Hot-swappable power and battery modules

  • USB, RS232 & EPO ports; support for SNMP/WEB card options

  • Front panel LEDs with detailed LCD monitoring and control screen

  • Expandable runtime with optional external battery packs

  • Hardwire input (4 wire split phase); L6-30R, C19 & 5-15/20R outlets

Availability: In stock

$7,799.99
Shipping Info
  • This item is in stock and ships within 1 business day
  • We will gladly accept returns for any reason within 30 days of receipt of delivery
  • Continental USA & Canada

Description

Details

Manufacturer: Tripp Lite
Model:  SU16000RT4U SmartOnline UPS 16kVA Online Double Conversion UPS, 8U Rack/Tower, 208/120V or 240/120V Hardwire+NEMA Outputs, Split phase input
Condition: Refurbished with New Batteries
Part Number: SU16000RT4U
Warranty: 1 Year Full Replacement Warranty, additional warranty available

 

SU16000RT4U Specifications:

OUTPUT

Output Volt Amp Capacity (VA)

16000

Output kVA capacity (kVA)

16

Output Watt Capacity (watts)

11200

Output kW capacity

11.2

Output power factor

0.7

Output Capacity Details

16,000 VA (240V) / 13,860 VA (208V) / 11,200 watts (208/240V)

Crest Factor

3:1

Nominal Output Voltage(s) Supported

120V; 208V; 240V

Nominal Voltage details

240/120V or 208/120V split phase output

Frequency compatibility

60 Hz

Output voltage regulation (line mode)

+/- 3%

Output voltage regulation (Economy line mode)

+/- 10%

Output voltage regulation (Battery mode)

+/- 3%

Built-in UPS output receptacles

5 5-15/20R outlet(s); 2 L6-30R outlet(s); 6 C19 outlet(s); Hardwire

Output circuit breaker

20A branch rated double pole breakers (x3) protect 2 C19 and 1 5-15/20R outlets each, 30A branch rated double pole breakers (x2) protect 1 L6-30R outlet each, 20A single pole breakers (x2) protect one 5-15/20R outlet each

Output AC waveform (AC mode)

Sine wave

Output AC waveform (battery mode)

Pure Sine wave

INPUT

Rated input current (at maximum load)

68A

Nominal Input Voltage(s) Supported

208V AC / 120V AC (4 wire split single phase); 240V AC /120V AC (4 wire split single phase)

UPS input connection type

Hardwire

UPS input connection description

4 wire split-phase input (L1, L2, N, G)

Recommended Electrical Service

70A 208/240-120 Split Phase

Phase

Single-Phase

BATTERY

Full load runtime (minutes)

5 min. (11,200w)

Half load runtime (minutes)

12 min. (5600w)

Expandable battery runtime

Supports extended runtime with optional external battery packs

External battery pack compatibility

BP192V18-4U; BP192V557C-16K; BP192V787C-16K; BP192V1037C-16K; BP192V1407C-16K

DC system voltage (VDC)

192

Battery recharge rate (included batteries)

Less than 6 hours from 10% to 80%

Battery replacement description

Hot-swappable, user replaceable batteries

VOLTAGE REGULATION

Voltage regulation description

Online, double-conversion power conditioning

Overvoltage correction

3% output voltage regulation during overvoltages to 140 (measured L1-N : L2-N)

Undervoltage correction

3% output voltage regulation during undervoltages to 65 (measured L1-N : L2-N)

LEDS ALARMS & SWITCHES

LED Indicators

6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options

Alarms

Unique audible alarms for all major UPS, environmental and power conditions (see manual)

Alarm cancel operation

Alarm cancel switch

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement

SURGE / NOISE SUPPRESSION

UPS AC suppression response time

Instantaneous

EMI / RFI AC noise suppression

Yes

PHYSICAL

Installation form factors supported with included accessories

4 post 19 inch rackmount

Included mounting accessory description

2 sets of adjustable 4 post rack rails included

Installation form factors supported with optional accessories

2 post rackmount (2POSTRMKITWM); Tower (2-9USTAND)

Optional mounting accessory notes

2 sets of 2POSTRMKITWM required for 2 post rackmount installation of separate power module and battery pack

Primary form factor

Rackmount

UPS / Power Module dimensions in primary form factor (height x width x depth / inches)

7 x 17.5 x 40.5

UPS / Power Module dimensions in primary form factor (height x width x depth / cm)

17.8 x 44.4 x 102.9

Installed whole system maximum rack depth (inches)

40.5

Installed whole system maximum rack depth (cm)

102.9

Rack Height

8U

Secondary form factor

Tower (requires 2-9USTAND)

UPS / Power Module weight (lbs)

86

UPS / Power Module weight (kg)

39

UPS dimensions details

Includes 4U power module and 4U battery pack

Included battery pack dimensions (height x width x depth / inches)

7 x 17.5 x 27.8

Included battery pack dimensions (height x width x depth / cm)

17.7 x 44.4 x 70.6

Included battery pack weight (lbs)

239

Included battery pack weight (kg)

108.5

UPS Shipping dimensions (height x width x depth / inches)

45.5 x 23.5 x 34.3

UPS Shipping dimensions (height x width x depth / cm)

115.6 x 59.7 x 87.1

Shipping weight (lbs)

448.8

Shipping weight (kg)

203.8

Cooling method

Fan

UPS housing material

Steel

ENVIRONMENTAL

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.

Relative Humidity

0 to 95%, non-condensing

AC mode BTU / hr. (full load)

5715

AC economy mode BTU / hr. (full load)

2441

Battery mode BTU / hr. (full load)

4249

Operating Elevation (ft.)

0-3000m (0 to 10,000 ft.)

Audible Noise

60 dBA at front side 1 meter

Operating Elevation (m)

0-3000 m

COMMUNICATIONS

Communications interface

USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface

Network monitoring port description

RS232 and contact closure communications are supported on one DB9 port

PowerAlert software

Included

Communications cable

USB and DB9 cabling included

LINE / BATTERY TRANSFER

Transfer time

No transfer time (0 ms.) in online, double-conversion mode

Low voltage transfer to battery power (setpoint)

65V (L1-N:L2-N)

High voltage transfer to battery power (setpoint)

140V (L1-N:L2-N)

SPECIAL FEATURES

Cold Start (startup in battery mode during a power failure)

Cold-start operation supported

High availability UPS features

Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module; Hot swappable batteries

Green & high efficiency features

High efficiency economy mode operation; Schedulable daily hours of economy mode operation

CERTIFICATIONS

UPS Certifications

Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); Meets FCC Part 15 Category A (EMI)

 

Additional Info

Additional Info

Input No
Output(VA) No
Type No
Output Voltage No