Eaton Powerware 9130 3000VA 2700W RM 2U 120V PW9130L3000R-XL2U - Refurbished

Eaton Powerware 9130 3000VA 2700W RM 2U PW9130L3000R-XL2U
Model: PW9130L3000R-XL2U
Input: NEMA L5-30P (120V - 30A)
Output: (6) NEMA 5-20R, (1) NEMA L5-30R
Double Conversion - Online UPS - Sine wave Output
New batteries, Refurbished UPS
1 Year Warranty Included

In stock

Manufacturer: Eaton Powerware
Model:
 Eaton Powerware 9130 3000VA 2700W, RM, 2U, 30A, 120V, New Batteries, Refurbished UPS
Condition:
New batteries, refurbished UPS
Part Number:
PW9130L3000R-XL2U

Maximum output: 2700W / 3000VA
Typical backup time
at half load: 13 minutes (1350 Watts)
Typical backup time
at full load: 5 minutes (2700 Watts)
Warranty:
1 year full replacement warranty


Eaton Powerware 9130 3000VA 2700W PW9130L3000R-XL2U - User Manual

 


PW9130L3000R-XL2U - Eaton Powerware 9130 3000VA Specifications:

General:

Topology

Online (Double Conversion)

Configuration

Rackmount

Catalog Number

PW9130L3000R-XL2U

Color

Black

Rating (VA/Watts)

3000/2700

Diagnostics

Full system self-test

UPS Bypass

Automatic bypass

Dimensions (H x W x D, inches)

3.4 x 17.2 x 23.6

Weight (lbs)

65

Rail Kit Included

Included with all rackmount units

Remote Emergency Power off (REPO)

Emergency shutdown control through the REPO port

Efficiency

>95% in high-efficiency mode; >86% in online mode


Input:

Connection

NEMA L5-30P

Input Cord

6 ft.

Input Voltage Range

90-144 VAC

Nominal Voltage

120V default (100/110/120/127V)

Frequency

50/60 Hz

Frequency Range

45–65 Hz

Nominal Current

25 A

Breaker Ratings

30A


Output:

Nominal Voltage

120V default (100/110/120/127V)

Output Receptacles

(6) NEMA 5-20R

(1) NEMA L5-30R

On Utility Voltage Regulation

±3% of nominal

On Battery Voltage Regulation

±3% of nominal

Power Factor

0.9

Frequency Regulation

±3% Hz online

Load Crest Factor

3 to 1


Battery:

Optional Extended Battery Module

PW9130N3000R-EBM2U

Maximum number of extended battery modules (EBM)

4

Battery Management

ABM technology

Battery Type

72 Vdc; (6) 12V, 9 Ah. Hot-swappable internal and external batteries.

Battery Replacement

EBP-1607

Start On Battery

Allows start of UPS without utility input

Recharge Time

Internal batteries: 3 hours. 1 EBM: 9 hours; 2 EBM: 15 hours; 3 EBM: 21 hours; 4 EBM: 27 hours


Communications:

User Interface

Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish

LEDs

Four status-indicating LEDs

Communication Ports

(1) USB, (1) RS-232 serial, Relay output (common alarm standard)

Communication Slot

Optional communication slots (BD Slot)

Power Management Software

Bundled software suite CD


Environmental & Standards:

RoHS Compliance

Yes

Heat Dissipation (BTU)

Line: 1257, Bat: 1755

Audible Noise

<50 dB

Operating Temperature

0°C to 40°C (32°F to 104°F) in online mode, with linear derating for altitude. NOTE:Thermal protection switches load to bypass in case of overheating

Safety markings

UL, cUL, VCCI

EMC Markings

FCC Class A, EN55022 Class A

Storage Temperature

-20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131°F) without batteries

Relative Humidity

5–90% non-condensing