Liebert Vertiv GXT4 6kVA 4.8kW RM 4U 120/208/240V
Model: GXT4-6000RT208 - 6000VA, 4800W
Input: Hardwire - Split Phase - 120/208-240V
Output: (4) 5-15/20R, (2) L6-30R (PD2-003 PDU Installed)
Double Conversion Online UPS - Sinewave Output
New batteries, Refurbished UPS
1 Year Warranty Included
Back Order
Manufacturer: Liebert
Model: Liebert GXT4 6000VA 4800W, RM, 4U, 208V, Split Phase, - PD2-003 PDU Installed - Output: (4) 15/20R, 2x L6-30R
Condition: New batteries, refurbished UPS
Part Number: GXT4-6000RT208
Maximum output: 4800W / 6000VA
Typical backup time at half load: 10 minutes (2400 Watts)
Typical backup time at full load: 5 minutes (4800 Watts)
Warranty: 1 year full replacement warranty
Includes: PD2-003 PDU Installed (Outputs provided: 4x 5-15/20R, 2x L6-30R
Liebert GXT4 6000VA 4800W RM 4U GXT4-6000RT208 User's Manual
GXT4-6000RT208 - Liebert GXT4 6000VA Specifications:
Physical:
|
Dimensions W x D x H Unit in. (mm) |
16.9 x 26.1 x 6.8 (430 x 662 x 173) |
|
Weight Unit, lb (kg) |
131.8 (69.9) |
Input AC Parameters:
|
Nominal Operating Frequency |
50 or 60Hz (Factory Default is 60Hz) |
|
Factory Default VAC |
120/208VAC at 120 degrees |
|
Factory Default L1-N, L2-N VAC |
120 VAC nominal |
|
Input Frequency w/o Battery Operation |
40 - 70 Hz |
|
Input Power Connection |
Hardwire Terminal Block 3W + G (L-L-N-G) |
|
L1-N, L2-N Maximum Allowable VAC |
150VAC |
Output AC Parameters:
|
Factory Default VAC |
120/208VAC @ 120 degrees |
|
Factory Default L1-N, L2-N VAC |
120VAC nominal |
|
User Configurable L1-N, L2-N VAC |
100/110/115/120/VAC, ±2% |
Overload Rating:
|
105% to 130% |
1 Minute |
|
131% to 150% |
10 seconds |
|
151% to 200% |
1 second |
|
>200% (impact load) |
At least 5 cycles |
Environmental:
|
Operating Temp °F (°C) |
32 to 104 (0 to 40)
|
|
Storage Temp °F (°C) |
5 to 122 (-15 to 50) |
|
Audible Noise |
Less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides |
|
Operating Elevation |
Up to 10,000 ft. (3000m) at 77°F (25°C) without derating |
|
Relative Humidity |
0% to 95%, non-condensing |
Agency:
|
Safety |
UL 1778, c-UL Listed
|
|
RFI/EMI |
FCC Class A |
|
Surge Immunity |
IEEE/ANSI C62.41 Category A & B |
|
Transportation |
ISTA Procedure 1E |
|
ENERGY STAR® qualified |
Yes |
PDU PD2-003 Specifications:
Physical:
|
Dimensions, W x D x H, Unit in (mm) |
5.2x15.5x3.5 (132x393x88)
|
|
Weight, lb (kg) |
10.8 (4.9) |
Electrical Specifications:
|
Amp Rating |
30A 2-pole input breaker for UPS input power
|
|
Input Power Connections |
L14-30P |
|
Output Power Connection |
(2) L6-30R |