Liebert Vertiv GXT4 6000VA 4800W RM 4U 120V/208V Split Phase GXT4-6000RT208 - Refurbished

Liebert Vertiv GXT4 6kVA 4.8kW RM 4U 120/208/240V
Model: GXT4-6000RT208 - 6000VA, 4800W
Input: Hardwire - Split Phase - 120/208-240V
Output: (4) 5-15/20R, (2) L6-30R (PD2-003 PDU Installed)
Double Conversion Online UPS - Sinewave Output
New batteries, Refurbished UPS
1 Year Warranty Included

Back Order

Manufacturer: Liebert
Model:
 Liebert GXT4 6000VA 4800W, RM, 4U, 208V, Split Phase, - PD2-003 PDU Installed - Output: (4) 15/20R, 2x L6-30R
Condition:
New batteries, refurbished UPS
Part Number:
GXT4-6000RT208

Maximum output: 4800W / 6000VA
Typical backup time
at half load: 10 minutes (2400 Watts)
Typical backup time
at full load: 5 minutes (4800 Watts)
Warranty:
1 year full replacement warranty
Includes: PD2-003 PDU Installed (Outputs provided: 4x 5-15/20R, 2x L6-30R


Liebert GXT4 6000VA 4800W RM 4U GXT4-6000RT208 User's Manual


GXT4-6000RT208 - Liebert GXT4 6000VA Specifications:

Physical:

Dimensions W x D x H Unit in. (mm)

16.9 x 26.1 x 6.8 (430 x 662 x 173)

Weight Unit, lb (kg)

131.8 (69.9)


Input AC Parameters:

Nominal Operating Frequency

50 or 60Hz (Factory Default is 60Hz)

Factory Default VAC

120/208VAC at 120 degrees

Factory Default L1-N, L2-N VAC

120 VAC nominal

Input Frequency w/o Battery Operation

40 - 70 Hz

Input Power Connection

Hardwire Terminal Block 3W + G (L-L-N-G)

L1-N, L2-N Maximum Allowable VAC

150VAC


Output AC Parameters:

Factory Default VAC

120/208VAC @ 120 degrees

Factory Default L1-N, L2-N VAC

120VAC nominal

User Configurable L1-N, L2-N VAC

100/110/115/120/VAC, ±2%


Overload Rating:

105% to 130%

1 Minute

131% to 150%

10 seconds

151% to 200%

1 second

>200% (impact load)

At least 5 cycles


Environmental:

Operating Temp °F (°C)

32 to 104 (0 to 40)

Storage Temp °F (°C)

5 to 122 (-15 to 50)

Audible Noise

Less than 55dBA at 3.2ft. (1m) rear; less than 50dBA at 3.2ft. (1m) front and sides

Operating Elevation

Up to 10,000 ft. (3000m) at 77°F (25°C) without derating

Relative Humidity

0% to 95%, non-condensing


Agency:

Safety

UL 1778, c-UL Listed

RFI/EMI

FCC Class A

Surge Immunity

IEEE/ANSI C62.41 Category A & B

Transportation

ISTA Procedure 1E

ENERGY STAR® qualified

Yes



PDU PD2-003 Specifications:

Physical:

Dimensions, W x D x H, Unit in (mm)

5.2x15.5x3.5 (132x393x88)

Weight, lb (kg)

10.8 (4.9)


Electrical Specifications:

Amp Rating

30A 2-pole input breaker for UPS input power

Input Power Connections

L14-30P

Output Power Connection

(2) L6-30R
(4) 5-15/20R T-slot