Manufacturer: Tripp Lite
Model: Tripp Lite SmartOnline UPS 3000VA 2700W, LCD, Tower, 120V
Condition: New batteries, refurbished UPS
Part Number: SU3000LCD2UHV
Maximum output: 2700W / 3000VA
Typical backup time at half load:13.5 minutes (1350 Watts)
Typical backup time at full load: 5 minutes (2700 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartOnline 3000VA 2700W Tower 120V SU3000LCD2UHV Manual
SU3000LCD2UHV - Tripp Lite SmartOnline 3000VA Specifications:
Input:
Rated input current (Maximum Load) |
14.97A |
||
Nominal Input Voltage(s) Supported |
200V AC; 208V AC; 220V AC; 230V AC; 240V AC |
||
UPS Input Connection Type |
|
||
Input Circuit Breakers |
40A |
||
UPS Input Cord Length (ft.) |
10 |
||
UPS Input Cord Length (m) |
3.1 |
||
Recommended Electrical Service |
20A 208V/240V |
||
Input Phase |
Single-Phase |
Output:
Output Volt Amp Capacity (VA) |
3000 |
||||
Output Capacity (kVA) |
3.0 |
||||
Output Watt Capacity (Watts) |
2700 |
||||
Output kW Capacity (kW) |
2.7 |
||||
Output Capacity Details |
ODE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 1890 watts for 208/220/230/240V output voltages; Max output is reduced to 2160W at 200V output voltage in all operating modes OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits). |
||||
Power Factor |
0.9 |
||||
Crest Factor |
3:1 |
||||
Nominal Voltage Details |
Nominal output voltage is user configured on first power-on |
||||
Frequency Compatibility |
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
||||
Frequency Compatibility Details |
Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation |
||||
Output Voltage Regulation (Line Mode) |
+/- 2% |
||||
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
||||
Output Voltage Regulation (Battery Mode) |
+/- 2% |
||||
Load Management Receptacles |
Two switchable outlet load banks (2 NEMA 6-15/20R outlets per bank) |
||||
Output AC Waveform (AC Mode) |
Pure Sine wave |
||||
Output AC Waveform (Battery Mode) |
Pure Sine wave |
||||
Nominal Output Voltage(s) Supported |
200V; 208V; 220V; 230V; 240V |
||||
Output Receptacles |
|
||||
Individually Controllable Load Banks |
Yes |
Battery:
Battery Type |
Valve Regulated Lead Acid (VRLA) |
Full Load Runtime (min.) |
5 min. (2700w) |
Half Load Runtime (min.) |
13.5 min. (1350w) |
Expandable Battery Runtime |
BP72V18-2US (multi-pack compatible) |
Expandable Runtime |
Yes |
Expandable Runtime Description |
External battery configurations require the use of Tripp Lite's External Battery Configuration Software, see manual for details |
DC System Voltage (VDC) |
72 |
Battery Recharge Rate (Included Batteries) |
Less than 3 hours from 10% to 90% (typical, full load discharge) |
Battery Access |
Front panel battery access door |
Internal UPS Replacement Battery Cartridge |
RBC72S |
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Voltage Regulation:
Voltage Regulation Description |
Online, double-conversion power conditioning |
Overvoltage Correction |
2% output voltage regulation during overvoltages to 150 |
Undervoltage Correction |
2% output voltage regulation during undervoltages to 160V (100% load), 130V (70% load), 100V (30% load) |
User Interface, Alerts & Controls:
Front Panel LCD Display |
Interactive front-panel LCD interface reports UPS operating mode, detailed UPS status and site-power information; LCD interface also enables a variety of advanced UPS setup and configuration options |
Switches |
5 front panel switches: On/Off, Up, Down and Escape |
Alarm Cancel Operation |
Power-fail alarm can be silenced by following on-screen prompts |
Audible Alarm |
Audible alarm indicates power failure, low battery, overload and fault |
LED Indicators |
S4 front panel LEDs: AC input (green), AC output (green), Battery (yellow), Fault (red) |
Surge / Noise Suppression:
UPS AC Suppression Joule Rating |
570 |
UPS AC Suppression Response Time |
Instantaneous |
UPS Dataline Suppression |
Single line dialup / network dataline protection included |
EMI / RFI AC Noise Suppression |
Yes |
Physical:
Primary Form Factor |
Rackmount
|
Cooling Method |
Fan
|
Primary UPS Depth (mm) |
616 |
Primary UPS Height (mm) |
88 |
Primary UPS Width (mm) |
438 |
Shipping Dimensions (hwd / cm) |
24.00 x 59.99 x 76.00 |
Shipping Weight (kg) |
39.01 |
Shipping Weight (lbs.) |
76.00 |
UPS Housing Material |
Metal |
UPS Power Module Dimensions (hwd, cm) |
8.79 x 43.79 x 61.60 |
UPS Power Module Weight (kg) |
32.12 |
Environmental:
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity |
5 to 95%, non-condensing |
AC Mode BTU / Hr. (Full Load) |
933 |
Battery Mode BTU / Hr. (Full Load) |
1399 |
AC Mode Efficiency Rating (100% Load) |
>90% |
Audible Noise |
<50dB at front side 1M |
Operating Elevation (m) |
0-10000 ft. (0-3000 m) |
Communications:
Network Management Cards |
WEBCARDLX |
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 plus assignable contact closure pin functions for On-battery, On bypass, Output-on and Low-battery conditions and remote Shutdown, Output-off, Reboot and Power-toggle operations |
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert |
Communications Cable |
USB and DB9 cabling included
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
Network Management Card Description |
Network management card optional |
Communications Interface |
Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled) |
Additional Info
Additional Info
Manufacturer | Tripp Lite |
---|---|
Form Factor | Tower |
Waveform in Battery Mode | Pure Sinewave |
Input Voltage | 240V AC |
Output (VA) | 3000VA |
Output Voltage | 208V AC, 230V AC (EU), 240V AC |
PDU Total Outlets | No |