APC Smart-UPS RT 6000VA 4200W RM 3U 208V to 208V/120V
Model: SURTD6000RMXLP3U
Input: NEMA L14-30P (208V - 30A)
Output: (1) NEMA L6-30R, (1) NEMA L14-30R, (4) NEMA 5-20R
Double Conversion Online UPS - Sinewave Output
New batteries, Refurbished UPS
1 Year Warranty Included
In stock
Manufacturer: APC
Model: APC Smart-UPS RT 6000VA 4200W, RM, 3U, 208V to 208V/120V
Condition: New batteries, refurbished UPS
Part Number: SURTD6000RMXLP3U
Maximum output: 4200W / 6000VA
Typical backup time at half load: 13.1 minutes (2200 Watts)
Typical backup time at full load: 4.4 minutes (4200 Watts)
Warranty: 1 year full replacement warranty
APC Smart-UPS RT 6000VA 4200W SURTD6000RMXLP3U - User Manual
Â
SURTD6000RMXLP3U - APC Smart-UPS Specifications:
Main:
|
Main Input Voltage |
208V |
||||||
|
Other Input Voltage |
240 V |
||||||
|
Main Output Voltage |
120V |
||||||
|
Other Output Voltage |
240V |
||||||
|
Rated Power in W |
4200W |
||||||
|
Rated Power in VA |
6000VA |
||||||
|
Input Connection Type |
|
||||||
|
Output Connection Type |
|
||||||
|
Number of Rack Unit |
3U |
||||||
|
Cable Length |
10 ft (3.05 m) |
||||||
|
Number of Cables |
1 |
||||||
|
Battery Type |
Lead-Acid Battery |
Batteries & Runtime:
|
Included Battery Modules |
2 |
|
Typical Recharge Time |
2.5 h |
|
RBC Quantity |
1 |
|
Additional Information |
Configurable for 208 or 240 nominal output voltage |
|
Battery Charge Power (Watts) |
382 W rated |
|
Battery Power in VAH |
960 VAh runtime |
|
Battery Life |
3 - 5 year(s) |
|
Replacement Battery |
APCRBC140 |
|
Battery Option |
SURT192RMXLBP3U 1 2880 VAh |
|
Extendable Run Time |
1 |
Â
General:
|
Number of Power Module Free Slots |
0 |
|
Number of Power Module Filled Slots |
0 |
|
Redundant |
No |
Physical:
|
Color |
Black |
|
Height |
5.12 in (13 cm) |
|
Width |
17.01 in (43.2 cm) |
|
Depth |
25.98 in (66 cm) |
|
Net Weight |
128.00 lb(US) (58.06 kg) |
|
Mounting Location |
Front |
|
Mounting Preference |
Lower |
|
Mounting Mode |
Rack-mounted |
|
Two Post Mountable |
0 |
|
USB Compatible |
No |
Input:
|
Input Frequency |
50/60 Hz +/- 5 Hz auto-sensing |
|
Efficiency at full load |
85 - 136 V adjustable |
Output:
|
Max Configurable Power (Watts) |
4200W |
|
Harmonic Distortion |
Less than 2% |
|
Output Frequency (sync to mains) |
50/60 Hz +/- 3 Hz user adjustable +/- 0.1 sync to mains |
|
Crest factor |
3 : 1 |
|
Topology |
Double Conversion Online |
|
Waveform Type |
Sine wave |
|
Bypass Type |
Internal Bypass (Automatic and Manual) |
|
Efficiency at full load |
90 % full load |
|
Maximum Configurable Power in VA |
6000VA |
Conformance:
|
Product Certifications |
CSA |
Environmental:
|
Ambient Air Temperature for Operation |
32 - 104 °F (0 - 40 °C) |
|
Relative Humidity |
0Â - 95 % non-condensing |
|
Operating Altitude |
0Â - 10000 ft |
|
Ambient Air Temperature for Storage |
5 - 113°F (-15 - 45°C) |
|
Storage Relative Humidity |
0Â - 95% non-condensing |
|
Storage Altitude |
0Â - 50000 ft (0.00Â - 15240.00 m) |
|
Acoustic Level |
55 dBA
|
|
Heat Dissipation |
1780 Btu/h |
|
IP degree of protection |
IP20 |
Communications & Management:
|
Free Slots |
0 |
|
Pre-Installed SmartSlotâ„¢ Cards |
Network management card 2 with environmental monitoring |
|
Alarm |
Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm |
|
Emergency Power Off (EPO) |
Yes |
Surge Protection and Filtering:
|
Surge Energy Rating |
480 J
|
|
Filtering |
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : m
|