Eaton 5PX 1000VA 1000W RM 2U 120V
Model: 5PX1000RT
Input: NEMA 5-15P (120V - 15A)
Output: (8) NEMA 5-15R
Line-Interactive UPS - Pure Sine Wave Output
Graphical LCD Display
ABM® Battery Management Technology
Extended Runtime - Supports Up to 4 External Battery Modules
New Batteries, Refurbished UPS
1 Year Full Replacement Warranty Included
In stock
Manufacturer: Eaton
Model:Â Eaton 5PX 1000VA 1000W Tower, 120V
Condition: New Batteries, Refurbished UPS
Part Number: 5PX1000RT
Maximum output: 1000WÂ /Â 1000VA
Typical backup time at half load: 16 minutes (500 Watts)
Typical backup time at full load: 7Â minutes (1000 Watts)
Warranty:Â 1 Year Full Replacement Warranty Â
Description : The Eaton 5PX1000RT is a 1000VA / 1000W line-interactive UPS designed for rackmount 2U installations, providing advanced power protection for servers, network equipment, storage devices, security systems, and other critical electronics. Featuring pure sine wave output, Automatic Voltage Regulation (AVR), ABM® battery management technology, a graphical LCD display, and support for external battery modules, the 5PX1000RT delivers reliable power protection with scalable runtime capability. It also features USB and RS-232 communication ports and an optional communication card slot for remote monitoring and management. Refurbished with new batteries and backed by a 1 Year Full Replacement Warranty
Â
Â
Â
Eaton 5PX - 1000VA 1000W RM 2U 120V 5PX1000RT - User Manual
Â
Â
5PX1000RT - Eaton UPS 1000VA - Specifications:
| General | Â | Â |
| Manufacturer | Eaton |  |
| Product Series | Eaton 5PX | Â |
| Model / Catalog Number | 5PX1000RT | Â |
| Product Type | Uninterruptible Power Supply (UPS) | Â |
| UPS Topology | Line-Interactive | Â |
| Rated Capacity | 1000VA | Â |
| Rated Power | 1000W | Â |
| Output Power Factor | 1.0 | Â |
| Output Waveform | Sine Wave | Â |
| Automatic Voltage Regulation (AVR) | Yes | Â |
| Form Factor | Rack Mount | Â |
| Rack Height | 2U | Â |
| Phase | Single Phase | Â |
| Color | Black / Silver | Â |
| Efficiency | Up to 99% | Â |
| Cold Start Capability | Yes | Â |
| Automatic Restart | Yes | Â |
| Self-Test Capability | Yes | Â |
| Load Segments | Yes – 2 Programmable Outlet Groups |  |
| Condition | New Batteries, Refurbished UPS | Â |
| Warranty | 1 Year Full Replacement Warranty Included | Â |
| Â | Â | Â |
| Input | Â | Â |
| Nominal Input Voltage | 120V Default | Â |
| Selectable Input Voltage | 100V / 110V / 120V / 127V | Â |
| Input Connection | NEMA 5-15P | Â |
| Input Cord | Attached | Â |
| Input Cord Length | 8 ft | Â |
| Input Voltage Range | 89–151 VAC |  |
| Extended Input Voltage Range | Adjustable down to 70 VAC | Â |
| Maximum Adjustable Input Range | 70–153 VAC |  |
| Nominal Input Frequency | 50/60 Hz | Â |
| Input Frequency Range – 50 Hz | 47–70 Hz |  |
| Input Frequency Range – 60 Hz | 56.5–70 Hz |  |
| Low Sensitivity Frequency Mode | Down to 40 Hz | Â |
| Input Power Factor | 1.0 | Â |
| Input Threshold Setting | Normal / Extended | Â |
| Input Sensitivity | High / Low Selectable | Â |
| Site Wiring Fault Detection | Yes | Â |
| Â | Â | Â |
| Output | Â | Â |
| Output Capacity | 1000VA | Â |
| Maximum Output Power | 1000W | Â |
| Nominal Output Voltage | 120V Default | Â |
| Selectable Output Voltage | 100V / 120V / 125V | Â |
| Output Voltage Range | 102–132 VAC |  |
| Output Frequency | 50/60 Hz | Â |
| Output Waveform | Sine Wave | Â |
| Output Power Factor | 1.0 | Â |
| Output Receptacles | (8) NEMA 5-15RÂ | |
| Primary Outlet Group | Yes | Â |
| Programmable Outlet Group 1 | (2) Programmable Outlets | Â |
| Programmable Outlet Group 2 | (2) Programmable Outlets | Â |
| Load Segment Control | Individual ON/OFF Control | Â |
| Automatic Load Shedding | Supported | Â |
| Load Segment Start Delay | Configurable | Â |
| Load Segment Shutdown Delay | Configurable | Â |
| Overload Pre-Alarm | Configurable | Â |
| Automatic Voltage Regulation (AVR) | Yes | Â |
| Â | Â | Â |
| Batteries & Runtime | Â | Â |
| Battery Type | Sealed Lead-Acid | Â |
| Battery Rating | 12V / 7.2Ah | Â |
| Battery Replacement | User Replaceable | Â |
| Hot-Swappable Battery | Yes | Â |
| Battery Management | Eaton ABM® Technology |  |
| Battery Charge Mode | ABM Cycling / Constant Charge Selectable | Â |
| Temperature-Compensated Charging | Yes | Â |
| Deep Discharge Protection | Yes | Â |
| Automatic Battery Test | Supported | Â |
| Battery Test Interval | Daily / Weekly / Monthly / Disabled | Â |
| Low Battery Warning Level | User Configurable | Â |
| Restart Battery Level | User Configurable | Â |
| Cold Start on Battery | Supported | Â |
| Extended Runtime Capability | Yes | Â |
| Compatible External Battery Module | 5PXEBM48RT | Â |
| Maximum External Battery Modules | Up to 4 | Â |
| EBM Voltage | 48V | Â |
| Automatic EBM Recognition | Yes | Â |
| EBM Quantity Detection | Automatic | Â |
| Typical Runtime at 1000W | 7 Minutes | Â |
| Runtime at 700W | Approx. 11 Minutes | Â |
| Runtime at 525W | Approx. 17 Minutes | Â |
| Runtime at 350W | Approx. 30 Minutes | Â |
| Runtime at 175W | Approx. 69 Minutes | Â |
| Runtime at 70W | Approx. 120 Minutes | Â |
| Runtime at 1000W + 1 EBM | Approx. 39 Minutes | Â |
| Runtime at 1000W + 2 EBMs | Approx. 71 Minutes | Â |
| Runtime at 1000W + 3 EBMs | Approx. 103 Minutes | Â |
| Runtime at 1000W + 4 EBMs | Approx. 135 Minutes | Â |
| Â | Â | Â |
| Communications & Management | Â | Â |
| User Interface | Graphical LCD Display | Â |
| LCD Controls | 5-Button Control Panel | Â |
| LCD Measurements | Load W/VA, Load A, Power Factor, Input V/Hz, Output V/Hz, Battery Status, Runtime & Efficiency | Â |
| Load Percentage Display | Yes | Â |
| Battery Capacity Display | Yes | Â |
| Estimated Runtime Display | Yes | Â |
| Efficiency Display | Yes | Â |
| Power Usage Measurement | Yes | Â |
| Event / Fault Log | Yes | Â |
| UPS Identification Display | Yes | Â |
| Firmware Information | Displayed Through LCD | Â |
| USB Communication Port | (1) USB | Â |
| Serial Communication Port | (1) RS-232 | Â |
| Simultaneous USB & RS-232 | No | Â |
| Communication Expansion Slot | (1) Optional Communication Card Slot | Â |
| Network Management | Supported | Â |
| Compatible Network Card | Eaton Card Network-MS, Network-M2 | Â |
| Power Management Software | Eaton Intelligent Power Manager | Â |
| Remote Commands | Supported | Â |
| Remote Shutdown / Restart | Supported | Â |
| Remote ON/OFF (ROO) | Supported | Â |
| Remote Power OFF (RPO) | Supported | Â |
| Programmable Outlet Management | Yes | Â |
| Â | Â | Â |
| User Interface & Controls | Â | Â |
| Display Type | Graphical LCD | Â |
| Control Buttons | Escape / Up / Down / Enter / On-Off | Â |
| Power Indicator | Green LED | Â |
| On-Battery Indicator | Yellow LED | Â |
| Alarm / Fault Indicator | Red LED | Â |
| Operating Mode Display | Yes | Â |
| AVR Mode Display | Yes | Â |
| Battery Mode Display | Yes | Â |
| Load Status | Yes | Â |
| Battery Status | Yes | Â |
| Estimated Backup Time | Yes | Â |
| Efficiency Information | Yes | Â |
| EBM Status | Yes | Â |
| Audible Alarm | Yes – User Configurable |  |
| Language Selection | English / French / German / Italian / Portuguese / Spanish / Russian | Â |
| LCD Brightness | Adjustable | Â |
| LCD Contrast | Adjustable | Â |
| Manual Battery Test | Yes | Â |
| Restore Factory Settings | Yes | Â |
| Reset Fault State | Yes | Â |
| Reset Power Usage Measurements | Yes | Â |
| Â | Â | Â |
| Power Management & Configuration | Â | Â |
| Cold Start | Enable / Disable | Â |
| Forced Reboot | Enable / Disable | Â |
| Automatic Restart | Enable / Disable | Â |
| Energy Saving Mode | Enable / Disable | Â |
| Sleep Mode | Enable / Disable | Â |
| Remote Commands | Enable / Disable | Â |
| Input Sensitivity | High / Low | Â |
| Input Threshold Mode | Normal / Extended | Â |
| Output Voltage Selection | Configurable | Â |
| Load Segment Auto Start Delay | Configurable | Â |
| Load Segment Auto Shutdown Delay | Configurable | Â |
| Overload Pre-Alarm | 5%–105% Configurable |  |
| Low Battery Warning | 10%–90% Configurable |  |
| Restart Battery Level | Configurable | Â |
| EBM Quantity Setting | 0–4 / Automatic Detection |  |
| Â | Â | Â |
| Physical | Â | Â |
| Rack Height | 2U | Â |
| Installation Type | Rack Mount | Â |
| Rack Compatibility | Standard 19-inch Rack | Â |
| Height | 3.4 in (86.2 mm) | Â |
| Width | 17.4 in (441.2 mm) | Â |
| Depth | 20.6 in (522 mm) | Â |
| Net Weight | Approx. 61.5–62 lb (27.9 kg) |  |
| Rack Mounting Hardware | Supported | Â |
| Front LCD Access | Yes | Â |
| Battery Front Access | Yes | Â |
| Â | Â | Â |
| Environmental | Â | Â |
| Operating Temperature | 32°F to 104°F (0°C to 40°C) |  |
| Storage Temperature | -15°C to +50°C |  |
| Relative Humidity | 20–95% Non-Condensing |  |
| Operating Altitude | Up to 10,000 ft (3000 m) Without Derating | Â |
| Audible Noise | <45 dB at 1 Meter | Â |
| Heat Dissipation – Online | 305 BTU/hr |  |
| Heat Dissipation – Battery | 2047 BTU/hr |  |
| Â | Â | Â |
| Compliance & Certifications | Â | Â |
| UL 1778 | Yes | Â |
| UL 497A | Yes | Â |
| UL Listed | Yes | Â |
| cUL Listed | Yes | Â |
| cTUVus | Yes | Â |
| NOM | Yes | Â |
| CE Marked | Yes | Â |
| FCC Compliance | FCC Part 15 Class A | Â |
| Performance Standard | IEC 62040-3 | Â |
| Surge Withstand | IEEE ANSI C62.41 Category A2 | Â |
Â