Eaton 9130 1500VAÂ RM 2U 120V
Model: PW9130L1500R-XL2U
Input: NEMA 5-15P (120V 15A)
Output: (6) NEMA 5-15R
Double Conversion, Online UPS
New batteries, refurbished UPS
1 Year Warranty Included
Back Order
Manufacturer: Eaton
Model:Â Eaton 9130 1500VA 1350W XL RM 2U 120V 15A
Condition: New batteries, refurbished UPS
Part Number:Â PW9130L1500R-XL2U
Maximum output: 1350W /Â 1500VA
Typical backup timeat half load: 14.0 minutes (675 Watts)
Typical backup time at full load: 5.0 minutes (1350 Watts)
Warranty: 1 year full replacement warranty
Eaton 9130 1500VA 1350W PW9130L1500R-XL2U - User Manual
Â
Â
PW9130L1500R-XL2U - Eaton Powerware UPS 1500VA Specifications:
| Â | |
|
General |
|
|
Configuration |
Rackmount |
|
Catalog Number |
PW9130L1500R-XL2U |
|
Color |
Black |
|
Rating (VA/Watts) |
1500/1350 |
|
Diagnostics |
Full system self-test |
|
UPS Bypass |
Automatic bypass |
|
Dimensions (H x W x D, inches) |
3.4 x 17.2 x 16.9 |
|
Weight (lbs) |
43 |
|
Warranty |
1 Year Replacement Warranty |
|
Rail Kit: |
Not included |
|
Remote Emergency Power off (REPO) |
Emergency shutdown control through the REPO port |
|
Efficiency |
>95% in high-efficiency mode; >86% in online mode |
|
 |
 |
|
Electrical Input |
|
|
Connection |
(1) NEMA 5-15P |
|
Input Cord |
6 ft. |
|
Input Voltage Range |
80-144 Vac |
|
Nominal Voltage |
120V default (100/110/120/127V) |
|
Frequency |
50/60 Hz |
|
Frequency Range |
45–65 Hz |
|
Nominal Current |
12.5 A |
|
Breaker Ratings |
15A |
|
 |
 |
|
Electrical Output |
 |
|
Nominal Voltage |
120V, 208V, 220–240V |
|
Output Receptacles |
(6) NEMA 5-15R |
|
On Utility Voltage Regulation |
±3% of nominal |
|
On Battery Voltage Regulation |
±3% of nominal |
|
Power Factor |
0.9 |
|
Frequency Regulation |
±3% Hz online |
|
Load Crest Factor |
3 to 1 |
|
 |
 |
|
Battery |
 |
|
Optional Extended Battery Module |
PW9130N1500R-EBM2U |
|
Maximum number of extended battery modules (EBM) |
4 |
|
Battery Management |
ABM technology |
|
Battery Type |
48 Vdc; (4) 12V, 9 Ah. Hot-swappable internal and external batteries. |
|
Battery Replacement |
EBP-1606 |
|
Start On Battery |
Allows start of UPS without utility input |
|
Recharge Time |
Internal batteries: 3 hours. 1 EBM: 9 hours; 2 EBM: 15 hours; 3 EBM: 21 hours; 4 EBM: 27 hours |
|
 |
 |
|
Communications |
 |
|
User Interface |
Graphical LCD with blue backlight and text in English, French, German, Russian and Spanish |
|
LEDs |
Four status-indicating LEDs |
|
Communication Ports |
(1) USB, (1) RS-232 serial, Relay output (common alarm standard) |
|
Communication Slot |
Optional communication slots (BD Slot) |
|
Power Management Software |
Bundled software suite CD |
|
 |
 |
|
Environmental & Standards |
|
|
RoHS Compliance |
Yes |
|
Heat Dissipation (BTU) |
Line: 750, Bat: 1011 |
|
Audible Noise |
<50 dB |
|
Operating Temperature |
0°C to 40°C(32°F to 104°F) in online mode, with linear derating for altitude. NOTE:Thermal protection switches load to bypass in case of overheating |
|
Safety markings |
UL, cUL, VCCI |
|
EMC Markings |
FCC Class B, EN55022 Class B |
|
Storage Temperature |
-20°C (-4°F) to +40°C (104°F) with batteries and -25°C (-13°F) to +55°C (131 °F) without batteries |
|
Relative Humidity |
5–90% non-condensing |
|
 |
 |