Liebert GXT4 1000VA 900W RM 2U Online UPS
Model: GXT4-1000RT120
Input: NEMA 5-15P (120V - 15A)
Output: (6) 5-15R
Online Double Conversion UPS - Sinewave Output
New batteries, Refurbished UPS
1 Year Warranty Included
Back Order
Manufacturer: Liebert
Model: Liebert GXT4 1000VA 900W RM 2U, 120V, 15A - Online double conversion UPS
Condition: New batteries, refurbished UPS
Part Number: GXT4-1000RT120
Maximum output: 900W / 1000VA
Warranty: 1 year full replacement warranty
Includes: (1) GXT4-1000RT120 UPS - No additional accessories are included
Liebert GXT4 1000VA 900W RM 2U GXT4-1000RT120 Manual
GXT4-1000RT120 - Liebert GXT4 1000VA Specifications:
Output:
|
Voltage |
110/115/120VAC (user-configurable); ±3% |
||
|
Waveform |
Sine wave |
||
|
Output Connections |
|
Input:
|
Voltage Range |
120VAC nominal; variable based on output load |
||
|
Frequency |
40Hz ~ 70Hz; Auto Sensing |
||
|
Input Connection Type |
|
||
|
Cord Length |
10 feet (3.04 meters) |
Batteries and Runtime:
|
Type |
Valve-regulated, non-spillable, lead acid |
|
Recharge Time |
5 Hours to 90% capacity after full discharge with 100% load till UPS auto-shutdown (Internal Batteries Only) |
Environmental:
|
Operating Temperature |
32° to 104°F (0° to 40°C) |
|
Storage Temperature |
19° to 122°F (-15° to 50°C) |
|
Relative Humidity |
0 to 95%, non-condensing |
|
Operating Elevation |
Up to 10,000 ft. (3000 m) at 77°F (25°C) without derating |
|
Storage Elevation |
50,000 ft. (15000 m) maximum |
|
Audible Noise |
<50 dBA, at 3ft. (1m) rear |
Physical:
|
Maximum Height |
3.4 inches (85 mm)
|
|
Maximum Width |
16.9 inches (430 mm) |
|
Maximum Depth |
16.2 inches (408 mm) |
|
Net weight |
47 lbs. (21 kg) |
|
Rack Height |
2U |
Agency:
|
Safety |
UL 1778, cUL Listed |
|
RFI/EMI |
FCC Class A |
|
Surge Immunity |
IEC 62040-2 2nd Ed |
|
Transportation |
ISTA Procedure 1A |