Liebert GXT5 1500VA 1500W RM 2U 230V Output:(8) IEC C13, GXT5-1500IRT2UXL - Refurbished

Liebert GXT5 1500VA 1500W RM 2U 230V
Model: GXT5-1500IRT2UXL
Input: IEC 60320 C14
Output: (8) IEC 60320 C13
Online Double Conversion UPS - Sinewave Output
New batteries, Refurbished UPS
1 Year Warranty Included

In stock

Manufacturer: Liebert
Model:
 Liebert GXT5 1500VA 1500W RM 2U, 230V
Condition:
New batteries, refurbished UPS
Part Number:
GXT5-1500IRT2UXL

Maximum output: 1500W / 1500VA
Typical backup time at half load: 16.3 minutes (750 Watts)
Typical backup time at full load: 5.6 minutes (1500 Watts)
Warranty: 1 year full replacement warranty
Includes: (1) GXT5-1500IRT2UXL UPS - No additional accessories are included


Liebert GXT5 1500VA 1500W RM 2U GXT5-1500IRT2UXL Manual


GXT5-1500IRT2UXL - Liebert GXT5 1500VA Specifications:

Output:

Factory-default
VAC Frequency

200/208/220/230/240VAC
(user-configurable); ±3%

Utility (AC) Mode
Overload

>200% for 250ms; 150- 200% for 2
seconds; 125- 150% for 50 seconds;
105-125% 60

Waveform

Sine wave

Output Connections

(8) C13


Input:

Rating

1500VA/1500W

Operating Frequency,
Nominal

40-70Hz; Auto Sensing

Voltage Range

Typical 230 VAC 

Input Connection Type

C14


Batteries and Runtime:

Type

Valve-regulated, non-spillable, lead acid

Typical Battery Recharge Time

4 Hour


Environmental:

Operating Temperature

32° to 104°F (0° to 40°C) (No Derating)

Storage Temperature

-15ºC to 40ºC (5ºF to 1104ºF)

Relative Humidity

0 to 95%, non-condensing

Operating Elevation

Up to 10,000 ft. (3000 m)

Audible Noise

<46dBA max at 1m front and sides
<43dBA at 1m rear


Physical:

Maximum Height

3.3 inches (85 mm)

Maximum Width

16.9 inches (430 mm)

Maximum Depth

18.5 inches (470 mm)

Net weight

46 lbs. (21 kg)

Rack Height

2U


Agency:

Surge Immunity

ANSI C62.41 Category B

Safety

EN 62040-1:2008+A1:2013

Emissions

EN 62040-2:2006
EN 61000-3-2:2014
EN 61000-3-3:2013

Transportation

ISTA Procedure 1A

Environmental

WEEE and ROHS2 REACH