Tripp Lite PDUMV30HV2 MTD Rack PDU, 5800W 208-240V 30A, Output:(40)C13 & (8)C19 - Refurbished

Tripp Lite PDUMV30HV2 5800W Metered Rack PDU, Zero U,  30A
Model: PDUMV30HV2
Input: NEMA L6-30P 200V/208V/240V
Output: (40) IEC 320 C13 (8) IEC 320 C19
Refurbished PDU
1 Year Warranty Included

Back Order

Manufacturer: Tripp Lite
Model:
 PDUMV30HV2
Description: Metered Rack PDU, Zero U, 30A, 208-240V, (40)C13 & (8)C19 - Refurbished
Input: NEMA L6-30P - 200V, 208V, 240V - 30A
Output: (40) C13 (8) C19
Condition: Refurbished
Warranty: 1 Year Full Replacement Warranty, additional warranty available

Tripp Lite PDUMV30HV2 Specifications: 

 

Input

PDU Input Voltage

200; 208; 220; 230; 240

Recommended Electrical Service

Single-phase 200/240V service

Maximum Input Amps

24A

Maximum Input Amps Details

Agency de-rated to 24A continuous

PDU Plug Type

NEMA L6-30P

Input Cord Length (ft.)

10

Input Cord Length (m)

3.05

Input Phase

Single-Phase


Output

Output Capacity Details

5.8kW (240V), 5kW (208V), 4.8kW (200V) total capacity / 30A max (Agency de-rated to 24A), 30A max per breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet

Frequency Compatibility

50 / 60 Hz

Output Receptacles

(40) C13; (8) C19

Output Nominal Voltage

200V; 208V; 240V

Overload Protection

Two 20A breakers protect 24 outlets each


Environmental

Operating Temperature Range

32 to122F (0 to 50C)

Storage Temperature Range

22° to 140°F (-30° to 60°C) 

Relative Humidity

5-95% non-condensing

Operating Elevation (ft.)

0-10000 ft. (0-3000 m) 

Operating Elevation (m)

0-3000


Physical

Shipping Dimensions (hwd / in.)

75.87 x 9.65 x 6.89

Shipping Dimensions (hwd / cm)

192.7 x 24.5 x 17.5

Shipping Weight (lbs.)

16.98

Shipping Weight (kg)

7.7

Unit Dimensions (hwd / in.)

70 x 2.17 x 2.52

Unit Dimensions (hwd / cm)

177.8 x 6.88 x 6.4

Unit Weight (lbs.)

12.35

Unit Weight (kg)

5.6

Material of Construction

Metal

Form Factors Supported

0u vertical installation in equipment racks, plus under-counter and wallmount

PDU Form Factor

Vertical (0U)