Tripp Lite Smart-Pro UPS 1500VA 900W Tower 120V SMC1500T - Refurbished

Tripp Lite Smart Pro 1500VA 900W Tower 120V
Model: SMC1500T
Input: NEMA 5-15P (120V - 15A)
Output: (8) NEMA 5-15R
Line-Interactive UPS - Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included

Back Order

Manufacturer: Tripp Lite
Model:
Tripp Lite SmartPro UPS 1500VA 900W,  Tower, 120V
Condition:
New batteries, refurbished UPS
Part Number:
SMC1500T

Maximum output: 900W / 1500VA
Typical backup time
at half load: 17.4 minutes (450 Watts)
Typical backup time
at full load: 6.4 minutes (900 Watts)
Warranty:
1 year full replacement warranty


Tripp Lite SmartPro 1500VA 900W Tower 120V SMC1500T Manual


SMC1500T - Tripp Lite SmartPro 1500VA Specifications:

Input:

Rated input current (Maximum Load)

10.1A (120V), 9.3A (110V), 8.6A (100V)

Nominal Input Voltage(s) Supported

100V AC; 110V AC; 120V AC AC

UPS Input Connection Type

NEMA 5-15P

UPS Input Cord Length (ft.)

6

UPS Input Cord Length (m)

2.1

Recommended Electrical Service

15A 120V

Input Phase

Single-Phase


Output:

Output Volt Amp Capacity (VA)

1500

Output Watt Capacity (Watts)

900

Nominal Voltage Details

120V default (voltage selection via back panel switches)

Frequency Compatibility

50 / 60 Hz

Frequency Compatibility Details

Automatic frequency selection

Output Voltage Regulation (Line Mode)

-13%, + 15%

Output Voltage Regulation (Battery Mode)

+/- 5%

Output AC Waveform (AC Mode)

Sine wave

Output AC Waveform (Battery Mode)

Pure Sine wave

Nominal Output Voltage(s) Supported

100V; 110V; 120V

Output Receptacles

(8) NEMA 5-15R

Individually Controllable Load Banks

No


Battery:

Battery Type

Valve Regulated Lead Acid (VRLA)

Full Load Runtime (min.)

6.4 min. (900w)

Half Load Runtime (min.)

17.4 min. (450w)

Expandable Runtime

No

DC System Voltage (VDC)

36

Battery Recharge Rate (Included Batteries) 

Less than 4.5 hours from 10% to 90% (typical, full load discharge)

Battery Access

Battery access door

Internal UPS Replacement Battery Cartridge

RBC36-SLT

Battery Replacement Description

Hot-swappable, user replaceable batteries


Voltage Regulation:

Voltage Regulation Description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 95 to 145 (120v), 87 to 133 (110v), 83 to 121 (100v)

Overvoltage Correction

Voltage reduction of 12% applies when input is 127 to 145 (120v), 116 to 133 (110v), 111 to 121 (100v)

Undervoltage Correction

Voltage boost of 14% applies when input is 95 to 108 (120v), 87 to 99 (110v), 83 to 90 (100v)


User Interface, Alerts & Controls:

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation; rear panel protected switches support nominal voltage selection

Alarm Cancel Operation

Power-fail alarm can be silenced using alarm-cancel switch

Audible Alarm

Audible alarm indicates power failure and overload conditions

LED Indicators

Status LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter for load and battery charge level

Site Wiring Fault Indication

Rear panel site wiring fault LED


Surge / Noise Suppression:

UPS AC Suppression Joule Rating

570

UPS AC Suppression Response Time

Instantaneous

UPS Dataline Suppression

1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet

EMI / RFI AC Noise Suppression

Yes


Physical:

Primary Form Factor

Tower

Cooling Method

Fan

Installation Form Factors Supported
with Included Accessories

Tower

Installation Form Factors Supported with Optional Accessories

Wallmount ( UPSWM - tower mounting kit)

Primary UPS Depth (mm)

335

Primary UPS Height (mm)

259

Primary UPS Width (mm)

173

Shipping Dimensions (hwd / in.)

14.00 x 9.60 x 18.30

Shipping Weight (lbs.)

43.90

UPS Housing Material

Steel

UPS Power Module Dimensions (hwd, in.)

10.2 x 6.8 x 13.2

UPS Power Module Weight (kg)

20.41

UPS Power Module Weight (lbs.)

45

 
Environmental:

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius.

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius.

Relative Humidity

5 to 95%, non-condensing

AC Mode BTU / Hr. (Full Load)

148

Battery Mode BTU / Hr. (Full Load)

500

AC Mode Efficiency Rating (100% Load)

95%


Communications:

Network Monitoring Port Description

Supports detailed monitoring of UPS and site power conditions

PowerAlert Software

For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert

Communications Cable

USB cabling included

WatchDog Compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications.

Network UPS Tools (NUT) Compatibility

NUT compatible. See a full list of NUT compatible Tripp Lite UPS systems at https://networkupstools.org/stable-hcl.html?manufacturer=Tripp%20Lite

Network Management Card Description

Network management not supported

Communications Interface

DB9 Serial; USB (HID enabled)