Tripp Lite SmartOnline 1000VA 800W RM 2U
Model: SUINT1000RTXL2UA
Input: C14 (200/208/220/230/240V)
Output: (6) C13
Type: Double Conversion Online UPS – Pure Sine Wave Output
Condition: New Batteries, Refurbished UPS
Warranty: 1 Year Included
In stock
Manufacturer: Tripp Lite
Model: Tripp Lite SmartOnline 1000VA 800W RM 2U
Condition: New Batteries, Refurbished UPS
Part Number: SUINT1000RTXL2UA
Maximum Output: 800W / 1000VA
Typical Backup Time at Half Load: 12 minutes (400W)
Typical Backup Time at Full Load: 4 minutes (800W)
Warranty: 1 year full replacement warranty
Tripp Lite SmartOnline 1000VA 800W RM 2U 200/240V SUINT1000RTXL2UA – User Manual
SUINT1000RTXL2UA - Tripp Lite SmartOnline 1000VA Specifications:
Input:
|
Rated input current (Maximum Load) |
5.1A (200V), 4.9A (208V), 4.6A (220V), 4.4A (230V), 4.2A (240V) |
|
Nominal Input Voltage(s) Supported |
200V; 208V; 220V; 230V; 240V AC |
|
UPS Input Connection Type |
IEC320-C14 |
|
Input Phase |
Single-Phase |
Output:
|
Output Volt Amp Capacity (VA) |
1000 |
|
Output Capacity (kVA) |
800 W |
|
Output Capacity Details |
Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for 30 seconds, >150% for 0.5 sec before switching to bypass or shutdown. |
|
Power Factor |
0.8 |
|
Crest Factor |
3:1 |
|
Nominal Voltage Details |
230V default (selectable 200/208/220/240V) |
|
Frequency Compatibility |
50 / 60 Hz |
|
Frequency Compatibility Details |
Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation |
|
Output Voltage Regulation (Line Mode) |
+/- 2% |
|
Output Voltage Regulation (Economy Line Mode) |
+/- 10% |
|
Output Voltage Regulation (Battery Mode) |
+/- 2% |
|
Output AC Waveform (AC Mode) |
Pure Sine wave |
|
Output AC Waveform (Battery Mode) |
Pure Sine wave |
|
Nominal Output Voltage(s) Supported |
200V; 208V; 220V; 230V; 240V |
|
Output Receptacles |
(6) C13 outlets |
|
Individually Controllable Load Banks |
No |
Battery:
|
Battery Type |
Valve Regulated Lead Acid (VRLA) |
|
Full Load Runtime (min.) |
4.5 minutes (800W) |
|
Half Load Runtime (min.) |
12.6 minutes (400W) |
|
Expandable Battery Runtime |
Yes, compatible with BP24V15RT2U, BP24V28-2U, BP24V70-3U, BP24V36-2US |
|
Expandable Runtime |
Yes |
|
DC System Voltage (VDC) |
24V |
|
Battery Recharge Rate (Included Batteries) |
<6 hours from 10% to 80% |
|
Battery Access |
Front panel battery access door |
|
Internal UPS Replacement Battery Cartridge |
RBC92-2U |
|
Battery Replacement Description |
Hot-swappable, user replaceable batteries |
Voltage Regulation:
|
Voltage Regulation Description |
Online, double-conversion power conditioning |
|
Overvoltage Correction |
Maintains ±2% output up to 275V |
|
Undervoltage Correction |
Maintains ±2% output down to 130V (under 70% load), 160V (>70% load) |
User Interface, Alerts & Controls:
|
Switches |
2 switches: Power On/Off and Alarm-Cancel/Self-Test |
|
Alarm Cancel Operation |
Power-fail alarm can be silenced by following on-screen prompts |
|
Audible Alarm |
Alerts for startup, power-failure, low battery, overload, UPS fault, remote shutdown |
| LED Indicators |
14 LEDs (line power, online, economy/bypass, on-battery, overload, battery low, replace battery, fault); 4-LED meter for load & battery |
| EPO Interface |
Yes, built-in |
Surge / Noise Suppression:
|
UPS AC Suppression Joule Rating |
1225 Joules |
|
UPS AC Suppression Response Time |
Instantaneous |
|
UPS Dataline Suppression |
TEL/DSL (1 in / 1 out), 10/100Base-T Ethernet |
|
EMI / RFI AC Noise Suppression |
Yes |
Physical:
|
Primary Form Factor |
Rackmount
|
|
Cooling Method |
Fan
|
|
Rack Height |
2U
|
|
UPS Dimensions (H x W x D) |
3.5 x 17.5 x 13.5 in / 8.89 x 44.45 x 34.29 cm |
|
UPS Weight |
41.8 lbs / 18.96 kg |
|
UPS Housing Material |
Steel |
Environmental:
|
Operating Temperature Range |
0–40°C / 32–104°F
|
|
Storage Temperature Range |
-15–50°C / 5–122°F |
|
Relative Humidity |
0–95%, non-condensing |
|
AC Mode BTU / Hr. (Full Load) |
408 BTU/hr |
|
Battery Mode BTU / Hr. (Full Load) |
444 BTU/hr |
|
AC Mode Efficiency Rating (100% Load) |
87% |
|
Operating Elevation (m) |
0-3000 m / 0–10000 ft |
Communications:
|
Network Management Cards |
TLNETCARD, WEBCARDLX, SNMPWEBCARD, MODBUSCARD . Optional |
|
Ports |
USB (HID), DB9 Serial, EPO, contact closure, slot for SNMP/Web |
|
PowerAlert Software |
Free downloadable PowerAlert software enables safe unattended file saves and system shutdown during prolonged power failures. https://tripplite.eaton.com/products/power-alert |
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
Network Management Card Description |
Network management card Optional |