Tripp Lite Double Conversion UPS 1500VA 1350W 200V/240V LCD SUINT1500LCD2U - Refurbished

Tripp Lite Smart-Online 1500VA 1350W RM 2U LCD
Model: SUINT1500LCD2U
Input: C14 (200/208/220/230/240V)
Output: (6) C13
Double Conversion Online UPS - Sine wave Output
New Batteries, Refurbished UPS
1 Year Warranty Included

Back Order

Manufacturer: Tripp Lite
Model:
Tripp Lite Smart-Online 1500VA 1350W RM 2U LCD
Condition:
New Batteries, Refurbished UPS
Part Number:
SUINT1500LCD2U

Maximum output: 1350W / 1500VA
Typical backup time
at half load:12.6 minutes (675 Watts)
Typical backup time
at full load: 4.5 minutes (1350 Watts)
Warranty:
1 year full replacement warranty


Tripp Lite SmartOnline 1500VA 1350W RM 2U 120V SUINT1500LCD2U - User Manual


SUINT1500LCD2U  - Tripp Lite SmartOnline 1500VA Specifications:

Input:

Rated input current (Maximum Load)

7.49A

Nominal Input Voltage(s) Supported

200V AC; 208V AC; 220V AC; 230V AC; 240V AC

UPS Input Connection Type

C14 inlet

Input Phase

Single-Phase


Output:

Output Volt Amp Capacity (VA)

1500

Output Capacity (kVA)

1.5

Output Watt Capacity (Watts)

1350

Output kW Capacity (kW)

1.35

Output Capacity Details

DE-RATING INFORMATION: Max output in Frequency Conversion mode is reduced to 945 watts for
208/220/230/240V output voltages; Max output is 1080W (756W in Frequency Conversion mode) at 200V output
voltage
OVERLOAD CAPACITY: Supports inverter operation up to 105% load continuously, 125% for 3 minutes, 150% for
30 seconds and >150% for 0.5 seconds before switching to BYPASS (when bypass input voltage and frequency are
WITHIN bypass limits) or SHUTDOWN (when bypass input voltage or frequency are OUTSIDE bypass limits).

Power Factor

0.9

Crest Factor

3:1

Nominal Voltage Details

Nominal output voltage is user configured on first power-on

Frequency Compatibility

50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion

Frequency Compatibility Details

Output frequency matches input nominal on startup; Output capacity de-rates by 30% during frequency conversion operation

Output Voltage Regulation (Line Mode)

+/- 2%

Output Voltage Regulation (Economy Line Mode)

+/- 10%

Output Voltage Regulation (Battery Mode)

+/- 2%

Load Management Receptacles

Two switchable outlet load banks (2 NEMA 6-15/20R outlets per bank)

Output AC Waveform (AC Mode)

Pure Sine wave

Output AC Waveform (Battery Mode)

Pure Sine wave

Nominal Output Voltage(s) Supported

200V; 208V; 220V; 230V; 240V

Output Receptacles

(6) C13 outlets

Individually Controllable Load Banks

Yes


Battery:

Battery Type

Valve Regulated Lead Acid (VRLA)

Full Load Runtime (min.)

4.5 minutes (1350W)

Half Load Runtime (min.)

12.6 minutes (675W)

Expandable Battery Runtime

Supports external battery packs such as BP36V15-2U and BP36V27-2US for extended runtime capabilities.

Expandable Runtime

Yes

Expandable Runtime Description

External battery configurations require the use of Tripp Lite's External Battery Configuration Software, see manual for details

DC System Voltage (VDC)

36V

Battery Recharge Rate (Included Batteries)

Less than 5.8 hours from 10% to 90% (typical, full load discharge)

Battery Access

Front panel battery access door

Internal UPS Replacement Battery Cartridge

RBC36S

Battery Replacement Description

Hot-swappable, user replaceable batteries


Voltage Regulation:

Voltage Regulation Description

Online, double-conversion power conditioning

Overvoltage Correction

Corrects output voltage regulation during overvoltages to 288V with a tolerance of +/- 2%

Undervoltage Correction

160V at 100% load
130V at 70% load
100V at 30% load


User Interface, Alerts & Controls:

Front Panel LCD Display

Interactive LCD interface provides UPS operating mode, detailed UPS status, and site-power information.
Allows for advanced setup and configuration options.

Switches

Five front panel switches: On/Off, Up, Down, and Escape.
Used for controlling UPS functions and navigating through settings.

Alarm Cancel Operation

Power-fail alarm can be silenced by following on-screen prompts

Audible Alarm

Alerts for power failure, low battery, overload, and fault conditions.
Provides audible notifications to indicate UPS status changes.

LED Indicators                                        

AC input (green): Indicates the presence of utility power input.AC output (green): Indicates the availability of AC power output from the UPS.
Battery (yellow): Indicates when the UPS is operating on battery power.
Fault (red): Indicates fault conditions or errors that may require attention.

Surge / Noise Suppression:

UPS AC Suppression Joule Rating

936 Joules

UPS AC Suppression Response Time

Instantaneous

UPS Dataline Suppression

Single line dialup / network dataline protection included

EMI / RFI AC Noise Suppression

Yes


Physical:

Primary Form Factor

Rackmount

Cooling Method

Fan

Primary UPS Depth (mm)


496 mm

Primary UPS Height (mm)

88 mm

Primary UPS Width (mm)

438 mm

Shipping Dimensions (hwd / cm)

24.00 x 57 x 70.00 cm

Shipping Weight (kg)

26.31 kg

Shipping Weight (lbs.)

58 lbs.

UPS Housing Material

Metal

UPS Power Module Dimensions (hwd, cm)

9 x 44 x 50 cm

UPS Power Module Weight (kg)


20.36

 
Environmental:

Operating Temperature Range

 0°C to 40°C (32°F to 104°F)

Storage Temperature Range

-15°C to 50°C (5°F to 122°F)

Relative Humidity

5 to 95%, non-condensing

AC Mode BTU / Hr. (Full Load)


330 BTU/hr

Battery Mode BTU / Hr. (Full Load)

689 BTU/hr

AC Mode Efficiency Rating (100% Load)

>93%

Audible Noise

<45dB at front side, 1 meter

Operating Elevation (m)

0-10000 ft. (0-3000 m)


Communications:

Network Management Cards

WEBCARDLX 

Network Monitoring Port Description

Includes ports such as RS-232 and USB for local monitoring and management.

PowerAlert Software

Free downloadable PowerAlert software enables safe unattended file saves and system shutdown during prolonged power failures. https://tripplite.eaton.com/products/power-alert

Communications Cable

USB and DB9 cabling included

WatchDog Compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

Network Management Card Description

Network management card optional

Communications Interface

Contact closure; DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)

 