Tripp Lite SmartOnline UPS 2200VA 1800W LCD RM 2U
Model: SU2200RTXLCD2U
Input: NEMA 5-20P (120V - 20A)
Output: (6) NEMA 5-15/20R, (1) NEMA L5-20R
Online Double Conversion UPS - Pure Sine Wave Output
LCD Monitoring & Control Display
Expandable Runtime with External Battery Packs
New batteries, Refurbished UPS
1 Year Warranty Included
In stock
Manufacturer:Â Tripp Lite
Model: Tripp Lite SmartOnline 2200VA 1800W, LCD, Rackmount 2U, 120V
Condition: New Batteries, Refurbished UPS
Part Number: SU2200RTXLCD2U
Maximum Output: 1800W / 2200VA
Input: NEMA 5-20P, 120V, 20A
Output: (6) NEMA 5-15/20R, (1) NEMA L5-20R
Topology: Online Double-Conversion
Waveform: Pure Sine Wave
Typical Backup Time at Half Load: 12 minutes (900W)
Typical Backup Time at Full Load: 4 minutes (1800W)
Warranty: 1 Year Full Replacement Warranty
Description: The Tripp Lite SU2200RTXLCD2U is a 2200VA / 1800W SmartOnline UPS designed for servers, network equipment, and critical IT systems. It features online double-conversion technology, pure sine wave output, an LCD display, and expandable runtime with optional external battery packs. The 2U rackmount design provides (6) NEMA 5-15/20R and (1) NEMA L5-20R outlets. New batteries, refurbished UPS with a 1 Year Full Replacement Warranty.
Â
Â
Tripp Lite SmartOnline 2200VA 1800W RM 120V SU2200RTXLCD2U - User Manual
Â
SU2200RTXLCD2U - Tripp Lite SmartOnline 2200VAÂ Specifications:
| General | Â | ||||
| Manufacturer | Tripp Lite | ||||
| Product Series | SmartOnline | ||||
| Model / Part Number | SU2200RTXLCD2U | ||||
| Rated Power | 2200VA / 1800W | ||||
| Topology | Online Double-Conversion | ||||
| Output Waveform | Pure Sine Wave | ||||
| Primary Form Factor | Rackmount | ||||
| Rack Height | 2U | ||||
| Cooling Method | Fan | ||||
| UPS Housing Material | Steel | ||||
| Front Panel Display | LCD Information and Configuration Display | ||||
| Condition | New batteries, refurbished UPS | ||||
| Warranty | 1 Year Full Replacement Warranty | ||||
| Â | Â | ||||
| Input | Â | ||||
| Nominal Input Voltage | 120V Factory Default | ||||
| Supported Input Voltages | 100V / 110V / 115V / 120V / 127V AC | ||||
|
UPS Input Connection Type |
|
||||
| Rated Input Current | 16A at Maximum Load | ||||
| Recommended Electrical Service | 20A, 120V | ||||
| Input Frequency | 50 / 60 Hz | ||||
| Input Phase | Single-Phase | ||||
| Input Cord Length | 10 ft (3.1 m) | ||||
| Â | Â | ||||
| Output | Â | ||||
| Output Capacity | 2200VA / 1800W | ||||
| Output Capacity (kVA / kW) | 2.2 kVA / 1.8 kW | ||||
| Nominal Output Voltage | 120V Factory Default | ||||
| Supported Output Voltages | 100V / 110V / 115V / 120V / 127V | ||||
|
Output Receptacles |
|
||||
| Output Power Factor | 0.82 | ||||
| Output Waveform – AC Mode | Pure Sine Wave | ||||
| Output Waveform – Battery Mode | Pure Sine Wave | ||||
| Crest Factor | 3:1 | ||||
| Output Voltage Regulation – Line Mode | ±2% | ||||
| Output Voltage Regulation – Economy Mode | ±10% | ||||
| Output Voltage Regulation – Battery Mode | ±3% | ||||
| Frequency Compatibility | 50 / 60 Hz | ||||
| Frequency Conversion | Supports 50-to-60 Hz and 60-to-50 Hz Conversion | ||||
| Battery Mode Frequency Regulation | ±0.05 Hz | ||||
| Load Management Receptacles | Two Switchable Three-Outlet 5-15/20R Load Banks | ||||
| Individually Controllable Load Banks | Yes | ||||
| Overload Capacity | Up to 105% Continuous; 125% for 3 Minutes; 150% for 30 Seconds | ||||
| Batteries & Runtime | Â | ||||
| Â | Â | ||||
| Battery Type | Valve Regulated Lead Acid (VRLA) | ||||
| DC System Voltage | 48V DC | ||||
| Typical Runtime at Half Load | 12 Minutes (900W) | ||||
| Typical Runtime at Full Load | 4 Minutes (1800W) | ||||
| Expandable Runtime | Yes | ||||
| External Battery Pack Compatibility | BP48V24-2U (Limit 1); BP48V60RT-3U (Multi-Pack); BP48V27-2US (Multi-Pack) | ||||
| Internal Replacement Battery Cartridge | RBC94-2U | ||||
| Battery Access | Front Panel | ||||
| Battery Replacement | Hot-Swappable, User Replaceable | ||||
| Recharge Time | Less than 3 Hours to 90% Typical | ||||
| Â | Â | ||||
| Voltage Regulation | Â | ||||
| Voltage Regulation Type | Online Double-Conversion | ||||
| Output Regulation | Maintains ±2% Output Voltage Regulation | ||||
| Overvoltage Correction | Corrects Overvoltages up to 150V at 0–100% Load | ||||
| Undervoltage Correction | Corrects Undervoltages to 100V at Full Load | ||||
| Severe Undervoltage Correction | Corrects Brownouts to 70V at 70% Load and 55V at 33% Load | ||||
| Â | Â | ||||
| User Interface, Alerts & Controls | Â | ||||
| Front Panel Display | LCD Information and Configuration Screen | ||||
| LCD Monitoring | UPS Status, Site Power Status and Operating Data | ||||
| LCD Configuration | Voltage, Frequency, Operating Mode and Alarm Settings | ||||
| Control Switches | Power On/Off, Alarm Cancel, Scroll and Select Controls | ||||
| Audible Alarm | UPS Startup, Power Failure, Low Battery, Overload, UPS Fault and Remote Shutdown | ||||
| Alarm Cancel | Yes | ||||
| Silent Alarm Mode | Configurable | ||||
| LED Indicators | 7 Front Panel Status LEDs | ||||
| LED Functions | Line Power, AC/DC Conversion, Battery, Inverter, ECO, Bypass and AC Output | ||||
| Â | Â | ||||
| Communications & Management | Â | ||||
| Communications Interface | Contact Closure, DB9 Serial, EPO, SNMP/Web Slot and USB | ||||
| USB Interface | Yes – HID Enabled | ||||
| DB9 Serial Interface | Yes | ||||
| Contact Closure | Yes | ||||
| Emergency Power Off (EPO) | Yes | ||||
| Network Management Slot | Yes | ||||
| Optional Network Management | Supported | ||||
| Compatible Network Cards | SNMPWEBCARD, TLNETCARD, WEBCARDLX | ||||
| Compatible Modbus Card | MODBUSCARD | ||||
| Compatible Relay Card | RELAYIOCARD | ||||
| Network Monitoring | Detailed UPS and Site Power Monitoring | ||||
| Communications Cables | USB and DB9 Cables Included | ||||
| Power Management Software | PowerAlert | ||||
| WatchDog Compatibility | Yes | ||||
| Remote Application Restart | Supported | ||||
| OS Restart | Supported | ||||
| Remote Hard-Reboot | Supported | ||||
| Â | Â | ||||
| Surge / Noise Suppression | Â | ||||
| Surge Energy Rating | 570 Joules | ||||
| Surge Response Time | Instantaneous | ||||
| Dataline Surge Protection | TEL/DSL and 10/100Base-T Ethernet | ||||
| EMI / RFI Noise Suppression | Yes | ||||
| Â | Â | ||||
| Physical | Â | ||||
| Rack Height | 2U | ||||
| Height | 3.5 in (89 mm) | ||||
| Width | 17.5 in (445 mm) | ||||
| Depth | 19 in (483 mm) | ||||
| UPS Weight | 48.5 lbs (22.0 kg) | ||||
| Included Rackmount Kit | 4POSTRAILKIT | ||||
| Included Rack Installation | 4-Post 19-Inch Rackmount | ||||
| Optional 2-Post Rackmount | Supported | ||||
| Optional Tower Installation | Supported with 2-9USTAND | ||||
| Optional Wall Mount | Supported | ||||
| Minimum Rack Depth without External Battery Pack | 24 in (61 cm) | ||||
| Minimum Rack Depth with External Battery Pack | 26 in (66 cm) | ||||
| Â | Â | ||||
| Environmental | Â | ||||
| Operating Temperature | 32–104°F (0–40°C) | ||||
| Storage Temperature | 5–122°F (-15–50°C) | ||||
| Relative Humidity | 0–95%, Non-Condensing | ||||
| Operating Elevation | Up to 3000 m | ||||
| Audible Noise | 57 dBA at 1 m | ||||
| AC Mode Heat Output – Full Load | 684 BTU/hr | ||||
| Economy Mode Heat Output – Full Load | 392 BTU/hr | ||||
| Battery Mode Heat Output – Full Load | 1085 BTU/hr | ||||
| Economy Mode Efficiency – Full Load | 94% |