Tripp Lite SmartPro 1200VA 700W LCD RM 2U
Model: SMART1200LCD
Input: NEMA 5-15P (120V - 15A)
Output: (8) NEMA 5-15R
Line-Interactive UPS - PWM Sinewave Output on Battery
New batteries, Refurbished UPS
1 Year Warranty Included
Back Order
Manufacturer: Tripp Lite
Model: Tripp Lite SmartPro UPS 1200VA 700W, LCD, RM, 2U, 120V
Condition: New batteries, refurbished UPS
Part Number: SMART1200LCD
Maximum output: 700W / 1200VA
Typical backup time at half load:14.3 minutes (350 Watts)
Typical backup time at full load: 4 minutes (700 Watts)
Warranty: 1 year full replacement warranty
Tripp Lite SmartPro 1200VA 700W RMÂ 120V SMART1200LCDÂ Manual
SMART1200LCD - Tripp Lite SmartPro 1200VAÂ Specifications:
Input:
|
Rated input current (Maximum Load) |
7A |
||
|
Nominal Input Voltage(s) Supported |
120V AC |
||
|
UPS Input Connection Type |
|
||
|
Input Circuit Breakers |
10A |
||
|
UPS Input Cord Length (ft.) |
6 |
||
|
UPS Input Cord Length (m) |
1.8 |
||
|
Recommended Electrical Service |
15A 120V |
||
|
Input Phase |
Single-Phase |
Output:
|
Output Volt Amp Capacity (VA) |
1200 |
||
|
Output Capacity (kVA) |
1.2 |
||
|
Output Watt Capacity (Watts) |
700 |
||
|
Nominal Voltage Details |
115v nominal output in battery mode |
||
|
Frequency Compatibility |
60 Hz |
||
|
Output Voltage Regulation (Line Mode) |
-18%, +8% |
||
|
Output Voltage Regulation (Battery Mode) |
+/- 5% |
||
|
Output AC Waveform (AC Mode) |
Sine wave |
||
|
Output AC Waveform (Battery Mode) |
PWM sine wave |
||
|
Nominal Output Voltage(s) Supported |
110V; 115V; 120V |
||
|
Output Receptacles |
|
||
|
Individually Controllable Load Banks |
No |
Battery:
|
Battery Type |
Valve Regulated Lead Acid (VRLA) |
|
Full Load Runtime (min.) |
4.0 min. (700w) |
|
Half Load Runtime (min.) |
14.3 min. (350w) |
|
DC System Voltage (VDC) |
24 |
|
Battery Recharge Rate (Included Batteries)Â |
Less than 4.5 hours from 10% to 90% |
|
Internal UPS Replacement Battery Cartridge |
IMPORTANT BATTERY REPLACEMENT INFORMATION > If your SMART1200LCD UPS has no battery replacement door, please contact a local electronics repair technician to source and install a matching replacement battery; If your SMART1200LCD UPS is equipped with a battery access door, please order Tripp Lite  RBC1500 (quantity 1) replacement battery |
|
Expandable Runtime |
No |
Voltage Regulation:
|
Voltage Regulation Description |
Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 75 to 147 |
|
Overvoltage Correction |
Input voltages between 128 and 147 are reduced by 12% |
|
Undervoltage Correction |
Input voltages between 92 and 107 are boosted by 14% |
|
Severe Undervoltage Correction |
Input voltages between 75 and 92 are boosted by 30% |
User Interface, Alerts & Controls:
|
Front Panel LCD Display |
Backlighted LCD screen offers detailed UPS status information, configuration options and Error message reporting; STATUS INFORMATION includes Input Voltage, Output Voltage, Estimated Runtime (minutes), Output Load Percentage, Output Load Wattage, Battery Charge Percentage, Graphical 5-Bar Battery Charge Level and UPS Operating Mode Display / CONFIGURATION OPTIONS include Power Sensitivity, LCD Status Information Scrolling, Alarm Disable, LCD Brightness and Self Test / REPORTED ERROR MESSAGES include Replace-Battery and Overload conditions; LCD Screen rotates for vertical or horizontal UPS placement |
|
Switches |
ON/OFF/MODE button provides UPS on/off power control (long-press) and advances the LCD screen display (short tap); MUTE/ENTER button provides temporary alarm cancel, plus selection and confirmation of on-screen configuration options |
|
Alarm Cancel Operation |
Press the MUTE/ENTER button during a power failure to silence the alarm; Once silenced, alarm will re-sound to indicate low-battery status |
|
Audible Alarm |
Audible alarm indicates power-failure and low-battery status; Alarm can be disabled entirely via front panel LCD interface (see manual) |
|
LED Indicators |
Front panel LCD display |
Surge / Noise Suppression:
|
UPS AC Suppression Joule Rating |
870 |
|
UPS AC Suppression Response Time |
Instantaneous |
|
UPS Dataline Suppression |
1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet |
|
UPS Dataline Suppression Details |
168 joules; Compatible with POE applications |
|
EMI / RFI AC Noise Suppression |
Yes |
Physical:
|
Primary Form Factor |
Rackmount |
|
Included Mounting Accessory Description |
Not included |
|
Installation Form Factors Supported with Included Accessories |
2 post 19 inch rackmount; 2 post front mount; 4 post 19 inch rackmount; Tower - Not included |
|
Minimum Required Rack Depth (cm) |
34.29 |
|
Minimum Required Rack Depth (inches) |
13.5 |
|
Primary UPS Depth (mm) |
267 |
|
Primary UPS Height (mm) |
89 |
|
Primary UPS Width (mm) |
440 |
|
Rack Height |
2U |
|
Shipping Dimensions (hwd / cm) |
18.54 x 38.35 x 54.10 |
|
Shipping Dimensions (hwd / in.) |
7.30 x 15.10 x 21.30 |
|
Shipping Weight (kg) |
12.93 |
|
Shipping Weight (lbs.) |
28.50 |
|
UPS Housing Material |
ABS |
|
UPS Power Module Dimensions (hwd, cm) |
8.86 x 44.02 x 26.67 |
|
UPS Power Module Dimensions (hwd, in.) |
3.49 x 17.33 x 10.5 |
|
UPS Power Module Weight (kg) |
12.05 |
|
UPS Power Module Weight (lbs.) |
26.56 |
Environmental:
|
Operating Temperature Range |
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
|
|
Storage Temperature Range |
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
|
Relative Humidity |
Up to 95%, non-condensing |
|
AC Mode BTU / Hr. (Full Load) |
80 |
|
AC Mode Efficiency Rating (100% Load) |
97% |
Communications:
|
Network Monitoring Port Description |
Supports detailed monitoring of UPS and site power conditions; DB9 provides contact-closure notification of AC Present (pins 1,9 connected) and AC Fail (pins 1,8 connected) |
|
PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert |
|
Communications Cable |
Not included |
|
WatchDog Compatibility |
Supports Watchdog application, OS and hard-reboot restart options for remote applications |
|
Network Management Card Description |
Network management not supported |
|
Communications Interface |
Contact closure; DB9 Serial; USB (HID enabled) |