Tripp Lite SmartPro 2200VA 1600W Tower 120V SMART2200SLT - Refurbished

Tripp Lite SmartPro 2200VA 1600W Tower
Model: SMART2200SLT
Input: NEMA 5-20P  (120V - 20A)
Output: (6) NEMA 5-15/20R,  (1) L5-20R
Line-Interactive UPS - Sine wave Output
New batteries, Refurbished UPS
1 Year Warranty Included

Back Order

Manufacturer: Tripp Lite
Model:
Tripp Lite SmartPro UPS 2200VA 1600W, Tower, 120V
Condition:
New batteries, refurbished UPS
Part Number:
SMART2200SLT

Maximum output: 1600W / 2200VA
Typical backup time
at half load: 13 minutes (800 Watts)
Typical backup time
at full load: 5 minutes (1600 Watts)
Warranty:
1 year full replacement warranty


Tripp Lite SmartPro 2200VA 1600W Tower 120V SMART2200SLT Manual


SMART2200SLT - Tripp Lite SmartPro Specifications:

Input:

Rated input current (Maximum Load)

15A

Nominal Input Voltage(s) Supported

120V AC

UPS Input Connection Type

(1) NEMA 5-20P

Input Circuit Breakers

20A

UPS Input Cord Length (ft.)

10

UPS Input Cord Length (m)

3.1

Recommended Electrical Service

20A 120V

Input Phase

Single-Phase


Output:

Output Volt Amp Capacity (VA)

2200

Output Capacity (kVA)

2.2

Output Watt Capacity (Watts)

1600

Output kW Capacity (kW)

1.6

Power Factor

0.7

Nominal Voltage Details

120v nominal output in battery mode

Frequency Compatibility

60 Hz

Output Voltage Regulation (Line Mode) 

-18% / +8%

Output Voltage Regulation (Battery Mode)

+/- 5%

Output AC Waveform (AC Mode)

Sine wave

Output AC Waveform (Battery Mode)

Pure Sine wave

Nominal Output Voltage(s) Supported

110V; 115V; 120V

Output Receptacles

(6) NEMA 5-15/20R

(1) NEMA L5-20R

Individually Controllable Load Banks

No


Battery:

Battery Type

Valve Regulated Lead Acid (VRLA)

Full Load Runtime (min.)

5 min. (1600w)

Half Load Runtime (min.)

13 min. (800w)

Expandable Runtime

No

DC System Voltage (VDC)

48

Battery Recharge Rate (Included Batteries) 

Less than 4.5 hours from 10% to 90% (typical, full load discharge)

Battery Access

Battery access door

Internal UPS Replacement Battery Cartridge

RBC54

Battery Replacement Description

Hot-swappable, user replaceable batteries


Voltage Regulation:

Voltage Regulation Description

Automatic voltage regulation (AVR) maintains line power operation with an input voltage range of 83V to overvoltages to 145V

Overvoltage Correction

Input voltages between 127 and 145 are reduced by 12%; Voltage setpoints subject to ±5% tolerance

Undervoltage Correction

Input voltages between 96 and 108V are boosted by 12%; Voltage setpoints subject to ±5% tolerance

Severe Undervoltage Correction

Input voltages between 83 and 95V are boosted by 24%; Voltage setpoints subject to ±5% tolerance


User Interface, Alerts & Controls:

Switches

2 Switches control off/on power status and alarm-cancel/self-test operation

Alarm Cancel Operation

Power-fail alarm can be silenced using alarm-cancel switch

Audible Alarm 

Audible alarm indicates power failure and overload conditions

LED Indicators

9 LEDs indicate line power, battery power, AVR, overload and replace battery status - with a 3-LED level meter for load and battery charge level


Surge / Noise Suppression:

UPS AC Suppression Joule Rating

570

UPS AC Suppression Response Time

Instantaneous

EMI / RFI AC Noise Suppression

Yes


Physical:

Primary Form Factor

Tower

Cooling Method

Fan

Installation Form Factors Supported with Included Accessories

Tower

Primary UPS Depth (mm)

318

Primary UPS Height (mm)

267

Primary UPS Width (mm)

226

Shipping Dimensions (hwd / cm)

39.12 x 36.32 x 43.69

Shipping Dimensions (hwd / in.)

15.40 x 14.30 x 17.20

Shipping Weight (kg)

31.34

Shipping Weight (lbs.)

69.10

UPS Housing Material

Steel

UPS Power Module Dimensions (hwd, cm)

26.67 x 22.61 x 31.75

UPS Power Module Dimensions (hwd, in.)

10.5 x 8.9 x 12.5

UPS Power Module Weight (kg)

25.85

UPS Power Module Weight (lbs.)

57


Environmental:

Operating Temperature Range

+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius

Storage Temperature Range

+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius

Relative Humidity

0 to 95%, non-condensing

AC Mode BTU / Hr. (Full Load)

287

Battery Mode BTU / Hr. (Full Load)

889

AC Mode Efficiency Rating (100% Load)

95%

Audible Noise

Audible Noise < 50 dBA at Front Side 1 Meter


Communications:

Network Management Cards

SNMPWEBCARD ;  WEBCARDLX ;  RELAYIOCARD

Network Monitoring Port Description

Supports detailed monitoring of UPS and site power conditions

PowerAlert Software

For local monitoring via the UPS’s built-in communication ports, download PowerAlert Local software at https://www.tripplite.com/poweralert

Communications Cable

USB and DB9 cabling included

WatchDog Compatibility

Supports Watchdog application, OS and hard-reboot restart options for remote applications

Network Management Card Description

Network management card optional

Communications Interface

DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface; USB (HID enabled)