Vertiv Liebert GXT5 6kVA 6kW RM 4U 120V/208V
Model: GXT5-6000MVRT4UXLN
Input: Hard-wired terminal block 3W + G (L-L-N-G)
Output: Hard-wired 3W + G (L-L-N-G)
Online, Double-Conversion UPS - Sine wave Output
New batteries, refurbished UPS
1 Year Warranty Included
In stock
Manufacturer: Vertiv
Model: Vertiv Liebert GXT5 6000VA 6000W RM 4U 120V/208V - Online Double Conversion UPS 3W + G (L-L-N-G)
Condition: New batteries, refurbished UPS
Part Number: GXT5-6000MVRT4UXLN
Maximum output: 6000W / 6000VA
Typical backup timeat half load: 9.5 minutes (3000 Watts)
Typical backup time at full load: 3.5 minutes (6000 Watts)
Warranty: 1 year full replacement warranty
Vertiv Liebert GXT5 6000VA 6000W 120V/208V GXT5-6000MVRT4UXLN User's Manual
GXT5-6000MVRT4UXLN - Vertiv GXT5 6kVA / 6kW Specifications:
Overview:
|
Power Rating |
6,000VA / 6,000W |
|
Input Voltage |
Typical: 208VAC / Range: 176-280VAC |
|
Output Voltage |
208/120VAC (user-configurable) |
|
Efficiency |
Up to 98% Active ECO Mode; up to 95% on-line mode |
|
Wiring |
Hardwired in/out; Optional PODs available |
Operational Conditions:
|
Operating Temperature |
+32 to +104 °F (0 to 40 °C) |
Physical:
|
Dimensions (inch/mm) |
16.9 × 25.6 × 6.8 (430×650×173) |
|
Weight (lbs/kg) |
125.6 (57) |
Input AC:
|
Operating Frequency, Nominal |
40 - 70 Hz (Factory Default is 60 Hz) |
|
Voltage Range |
176 - 280 VAC |
|
Input Wiring |
Hard-wired terminal block 3W + G (L-L-N-G) |
Output AC:
|
Output Receptacles |
|
|
|
User Selectable Output |
208/120VAC |
|
|
Output Voltage |
208/120VAC (user-configurable) |
|
|
Waveform (on battery) |
Sine wave |
|
|
Utility (AC) Mode Overload |
105% to 125% for 5 minutes |
Interfaces / Ports:
|
Interface Options |
Factory pre-installed Vertiv™ RDU101 SNMP/Webcard, USB, RS485, RS232, terminal block, external battery connector |
|
Protocols |
SNMP and web management enabled with factory pre-installed Vertiv RDU101 communications card; serial connection for out-of-band management |
|
Control Panel |
Full-color graphic LCD with gravity sensing orientation, provides insight to UPS status for easy installation, configuration and operation |
Battery Parameters:
|
Type |
Valve-regulated, non-spillable, lead acid |
|
Backup Time (100% Load) |
3.5 Minutes |
|
Backup Time (50% Load) |
9.5 Minutes |
|
+1 External Battery Cabinet (100% Load) |
9.5 Minutes |
|
+1 External Battery Cabinet |
25.5 Minutes |
Environmental:
|
Operating Temperature, °F (°C) |
+32 to +104 (0 to 40) (no derating) |
|
Storage Temperature, °F (°C ) |
+5 to +104 (-15 to 40) |
|
Relative Humidity |
0% to 95%, non-condensing |
|
Operating Elevation |
Up to 10,000 ft (3,000 m) at 77°F (25°C) without derating |
|
Audible Noise |
<50 dBA,at 3.2 ft (1 m) |
Agency:
|
Surge Immunity |
IEEE/ANSI C62.41 Category A & B |
|
Safety |
UL1778, c-UL listed |
|
Transportation |
ISTA Procedure 1E |
|
Emissions |
FCC Part 15 (Class A) |
Miscellaneous:
|
Listings |
ENERGY STAR® 2.0 certified, UL1778, c-UL listed, RoHS2, REACH |
|
Topology |
On-line double conversion UPS; flexible rack/tower form factor |